| 2022-03-25 18:19:19 | 2ND PRIVATE PROVIDER AUDIT FBC-2020 RESIDENTIAL |
| | PERMIT-21100601 |
| | |
| | |
| | BUILDING AUDIT RESULTS: DENIED. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) WILL COMPLY. SEPARATE PERMITS ARE REQUIRED FOR THE |
| | GENERATOR, DRIVEWAY, LANDSCAPING, ELEVATOR, LAWN |
| | SPRINKLERS, POOLS, SITE WALLS AND FENCES. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) NOT COMPLIED. [THE MAXIMUM DESIGN PRESSURES IN NEW |
| | NOA NO. 20-1015.18 ARE +48 PSF AND -52 PSF. THIS DOES |
| | NOT MEET THE -61.1 PSF REQUIRED NEGATIVE PRESSURE FOR |
| | THE OPENING.]THE WIND PRESSURES FOR THE 9' GARAGE DOOR |
| | ARE SPECIFIED ON SHEET S5.00 AS +47.2 PSF, -61.1 PSF. |
| | THE MAXIMUM NEGATIVE PRESSURE ON THE PRODUCT APPROVAL |
| | FOR THE GARAGE DOORS IS -60.3 PSF, WHICH IS LESS THAN |
| | THE ENGINEER HAS SPECIFIED FOR THAT OPENING. FBC |
| | 107.3.4 |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) NOT COMPLIED. [ THE WALL SECTION STILL SHOWS SOFFIT |
| | VENTS AND THE INSULATION IS SHOWN AT THE CEILING AND |
| | NOT UNDERNEATH THE ROOF SHEATHING. ] ON SHEET A3.2, THE |
| | WALL SECTION SHOWS SPRAY FOAM INSULATION ON THE BOTTOM |
| | CORD OF THE TRUSSES AND SOFFIT VENTS FOR THE ATTIC |
| | SPACE. THE ENERGY EFFICIENCY FORM SPECIFIES AN UNVENTED |
| | ATTIC. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW |
| | SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN |
| | CASEMENT WINDOWS.] THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED FOR THE KOLBE CASEMENT WINDOWS HAS A MAXIMUM |
| | FRAME HEIGHT OF 72 INCHES (6 FT.) FOR THE HALF-ROUND |
| | WINDOWS. THE WINDOW SCHEDULE ON SHEET A-3.3 HAS SOME |
| | WINDOWS THAT ARE 108 INCHES (9 FT.) IN HEIGHT. SUBMIT |
| | PRODUCT APPROVALS FOR THE 9 FT TALL KOLBE WINDOWS. FBC |
| | 107.3.4 |
| | |
| | 12) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW |
| | SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN |
| | CASEMENT WINDOWS.] SUBMIT PRODUCT APPROVALS FOR THE |
| | SIGNATURE BRAND 9 FT TALL "CEDAR" CASEMENT WINDOWS. FBC |
| | 107.3.4 |
| | |
| | 13) COMPLIED. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) PARTIALLY COMPLIED. [ I DID NOT SEE THE NOTE FOR |
| | THE WATERPROOFING IN SECTION 3.2/S-1 ON SHEET A-3.2. ] |
| | SPECIFY HOW THE FLOOR OF THE FRONT AND REAR BALCONIES |
| | WILL BE WATERPROOFED. FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |