| 2022-02-25 11:00:55 | 1ST PRIVATE PROVIDER AUDIT FBC-2020 RESIDENTIAL |
| | PERMIT-21100601 |
| | |
| | |
| | BUILDING AUDIT RESULTS: DENIED. |
| | |
| | 1) IN THE SUPPORTING DOCUMENTS THERE IS A BLANK |
| | CONDITIONAL APPROVAL FORM FOR LANDSCAPE AND LAWN |
| | SPRINKLER. PLEASE COMPLETE THE FORM OR REMOVE IT. FBC |
| | 107.2.1 |
| | |
| | 2) SEPARATE PERMITS ARE REQUIRED FOR THE GENERATOR, |
| | DRIVEWAY, LANDSCAPING, ELEVATOR, LAWN SPRINKLERS, |
| | POOLS, SITE WALLS AND FENCES. |
| | |
| | 3) THE PRODUCT APPROVAL FOR THE TU PLUS ROOF TILE |
| | UNDERLAYMENT EXPIRED ON 9/13/2021. SUBMIT A CURRENT |
| | PRODUCT APPROVAL. FBC 107.3.4 |
| | |
| | 4) THE WIND PRESSURES FOR THE 9' GARAGE DOOR ARE |
| | SPECIFIED ON SHEET S5.00 AS +47.2 PSF, -61.1 PSF. THE |
| | MAXIMUM NEGATIVE PRESSURE ON THE PRODUCT APPROVAL FOR |
| | THE GARAGE DOORS IS -60.3 PSF, WHICH IS LESS THAN THE |
| | ENGINEER HAS SPECIFIED FOR THAT OPENING. FBC 107.3.4 |
| | |
| | 5) ON SHEET A-0.00, GENERAL NOTE #1 STATES THAT THE |
| | CONSTRUCTION IS TO FOLLOW THE TOWN OF PALM BEACH |
| | AMENDMENTS AND THIS PROJECT IS LOCATED IN THE CITY OF |
| | WEST PALM BEACH. PLEASE CORRECT. FBC 107.2.1 |
| | |
| | 6) THE DRAINAGE PLAN DOES NOT HAVE THE ELEVATIONS OF |
| | THE RIGHT OF WAY AT THE FRONT OF THE HOUSE OR THE |
| | ADJACENT PROPERTIES. FBC 107.2.1 |
| | |
| | 7) ON SHEET A3.2, THE WALL SECTION SHOWS SPRAY FOAM |
| | INSULATION ON THE BOTTOM CORD OF THE TRUSSES AND SOFFIT |
| | VENTS FOR THE ATTIC SPACE. THE ENERGY EFFICIENCY FORM |
| | SPECIFIES AN UNVENTED ATTIC. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 8) SHOW COMPLIANCE WITH FBC-R807.1 FOR REQUIRED ATTIC |
| | SPACE. |
| | |
| | 9) THE ROOF SHEATHING NAILING SCHEDULE SPECIFIES 10D |
| | COMMON NAILS AT 6"OC. FBC-R803.2.3.1 AND TABLE R803.2.1 |
| | REQUIRES THE ROOF SHEATHING TO BE NAILED 4" OC WITH |
| | RING SHANK NAILS MEETING THE SPECIFICATIONS IN ASTM |
| | F1667. FOOTNOTE A ALLOWS SHEATHING LOCATED A MINIMUM OF |
| | 4 FEET FROM THE PERIMETER EDGE OF THE ROOF, INCLUDING 4 |
| | FEET ON EACH SIDE OF RIDGES AND HIPS TO BE NAILED AT 6 |
| | INCHES O.C. PLEASE REVISE THE PLANS OR SUBMIT |
| | CALCULATIONS THAT SHOW THE NAILING THAT IS SPECIFIED ON |
| | THE PLANS EQUIVALENT OR BETTER. |
| | |
| | 10) SHOW COMPLIANCE WITH FBC-R 312.1 FOR THE BALCONY |
| | GUARDS. |
| | |
| | 11) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | KOLBE CASEMENT WINDOWS HAS A MAXIMUM FRAME HEIGHT OF 72 |
| | INCHES (6 FT.) FOR THE HALF-ROUND WINDOWS. THE WINDOW |
| | SCHEDULE ON SHEET A-3.3 HAS SOME WINDOWS THAT ARE 108 |
| | INCHES (9 FT.) IN HEIGHT. SUBMIT PRODUCT APPROVALS FOR |
| | THE 9 FT TALL KOLBE WINDOWS. FBC 107.3.4 |
| | |
| | 12) SUBMIT PRODUCT APPROVALS FOR THE SIGNATURE BRAND 9 |
| | FT TALL "CEDAR" CASEMENT WINDOWS. FBC 107.3.4 |
| | |
| | 13) SUBMIT PRODUCT APPROVALS FOR THE SIGNATURE BRAND 9 |
| | FT TALL X 3 FT- 7 IN "CEDAR" FRONT DOOR. FBC 107.3.4 |
| | |
| | 14) THE FIRST FLOOR PLAN APPEARS TO SHOW A FIREPLACE AT |
| | THE COVERED LOGGIA. THERE ARE NO OTHER DETAILS |
| | PROVIDED. PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 15) SPECIFY HOW THE FLOOR OF THE FRONT AND REAR |
| | BALCONIES WILL BE WATERPROOFED. FBC 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |