| 2021-12-01 12:06:08 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. SUBMITTED MIAMI-DADE COUNTY NOA 18-0919.12 SYSTEM |
| | E(2) FASTENING OPTION #1 MAXIMUM DESIGN PRESSURE -45 DO |
| | NOT MEET EXPOSURE CATEGORY C; ZONE 2 MINIMUM DESIGN |
| | PRESSURE REQUIREMENT OF -79.38 OR ZONE 3 MINIMUM DESIGN |
| | PRESSURE REQUIREMENT OF -108.17. NEITHER RATIONAL |
| | ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR |
| | ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E. |
| | PERIMETERS, EXTENDED CORNERS AND CORNERS). AS PER |
| | LIMITATIONS #9. SELECT AS SYSTEM THAT MEETS OR EXCEEDS |
| | THE ABOVE REQUIREMENTS. ENGINEERED SIGNED AND SEALED |
| | CALCULATIONS MAY BE REQUIRED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |