Plan Review Notes
Plan Review Notes For Permit 21100584
Permit Number 21100584
Review Stop B
Sequence Number 6
Notes
Date Text
2021-12-01 12:06:08JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 18-0919.12 SYSTEM
 E(2) FASTENING OPTION #1 MAXIMUM DESIGN PRESSURE -45 DO
 NOT MEET EXPOSURE CATEGORY C; ZONE 2 MINIMUM DESIGN
 PRESSURE REQUIREMENT OF -79.38 OR ZONE 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT OF -108.17. NEITHER RATIONAL
 ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR
 ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E.
 PERIMETERS, EXTENDED CORNERS AND CORNERS). AS PER
 LIMITATIONS #9. SELECT AS SYSTEM THAT MEETS OR EXCEEDS
 THE ABOVE REQUIREMENTS. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  