| Plan Review Notes For Permit 21100584 |
| Permit Number |
21100584 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-11-05 18:59:07 | ****CORRECTIONS**** | | | COURTESY REVIEW UPON REQUEST OF LIZZ TREVINO, | | | PERMITTING DEPARTMENT | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SEE PREVIOUS LISTS. THE PRODUCT APPROVAL SUBMITTED | | | DOES NOT INDICATE WHICH OF THE APPROVED ASSEMBLIES IS | | | PROPOSED. SEE PAGES 7 THROUGH 16 FOR ASSEMBLY OPTIONS. | | | ONE MUST BE SELECTED. | | | | | | 2. SEE THE PALM BEACH COUNTY WIND LOAD CHART. THIS | | | DOCUMENT WAS SENT VIA EMAIL. NONE OF THE ASSEMBLIES | | | MEET THE DESIGN PRESSURE FOR ZONE 3 (-109) SO | | | ENGINEERING IS REQUIRED. | | | | | | FBC R 301 | | | | | | | | | | | | |
|