| 2021-10-19 10:23:10 | 10/19/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF EXISTING |
| | GAS PERMITS WITH INSPECTIONS OF THE CURRENT SYSTEM, AND |
| | ONE WAS SENT TO YOUR EMAIL. PLEASE INCLUDE THE EXISTING |
| | AND NEW GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR |
| | THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | 2. WOULD YOU PLEASE PROVIDE THE DEVELOPED LENGTH TO THE |
| | FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE, |
| | THE TYPE OF GAS, AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL GAS. |
| | |
| | 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 4. FUTURE GAS APPLIANCE CONNECTION HARD-CAPPED A VALVED |
| | PER THE 2020 RES. SECS. G2415, G2422.1. |
| | |
| | 5. WOULD YOU PLEASE SHOW AND LABEL ALL SHUTOFF VALVES |
| | SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP |
| | REGULATOR AND OR APPLIANCE PER THE 2020 FBC RES. SEC. |
| | G2420.4. |
| | |
| | 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 8. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC |
| | RES. SEC G2421.2. |
| | |
| | 9. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | 10. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON |
| | EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE, |
| | DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 11. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1 OR 410.1. |
| | |
| | 12. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 13. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 14. GAS UNITS MAY REQUIRE CONDENSATE, AND IF SO, IT |
| | NEEDS TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC |
| | SEC R318.5. |
| | |
| | 15. WOULD YOU PLEASE PROVIDE MANUFACTURES |
| | SPECIFICATIONS FOR ALL NEW AND FUTURE EQUIPMENT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 16. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR |
| | IGNITION SOURCE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 17. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |