Plan Review Notes
Plan Review Notes For Permit 21100573
Permit Number 21100573
Review Stop G
Sequence Number 1
Notes
Date Text
2021-10-19 10:23:1010/19/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF EXISTING
 GAS PERMITS WITH INSPECTIONS OF THE CURRENT SYSTEM, AND
 ONE WAS SENT TO YOUR EMAIL. PLEASE INCLUDE THE EXISTING
 AND NEW GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR
 THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 2. WOULD YOU PLEASE PROVIDE THE DEVELOPED LENGTH TO THE
 FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE,
 THE TYPE OF GAS, AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 4. FUTURE GAS APPLIANCE CONNECTION HARD-CAPPED A VALVED
 PER THE 2020 RES. SECS. G2415, G2422.1.
  
 5. WOULD YOU PLEASE SHOW AND LABEL ALL SHUTOFF VALVES
 SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR AND OR APPLIANCE PER THE 2020 FBC RES. SEC.
 G2420.4.
  
 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 8. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC
 RES. SEC G2421.2.
  
 9. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 10. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON
 EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE,
 DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 11. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1 OR 410.1.
  
 12. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 14. GAS UNITS MAY REQUIRE CONDENSATE, AND IF SO, IT
 NEEDS TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC
 SEC R318.5.
  
 15. WOULD YOU PLEASE PROVIDE MANUFACTURES
 SPECIFICATIONS FOR ALL NEW AND FUTURE EQUIPMENT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 16. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR
 IGNITION SOURCE PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 17. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  