Plan Review Notes
Plan Review Notes For Permit 21100549
Permit Number 21100549
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-15 12:09:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A/C DUCT THAT APPEAR TO BE
 PENETRATING FIRE RATED WALLS A SEVERAL LOCATIONS.
  
 THIS ARE NO INDICATIONS THAT THERE ARE EXISTING FIRE
 DAMPERS AT THESE LOCATIONS, WHETHER A FIRE DAMPER IS
 REQUIRED, OR NEW ONES WILL BE INSTALLED.
  
 PER NFPA 90 A
  
 5.3* PENETRATIONS ? PROTECTION OF OPENINGS.
 5.3.1 FIRE-RATED WALLS AND PARTITIONS.
 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE
 AIR
 DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR
 PARTITIONS
 REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR
 MORE.
 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE
 OTHER
 OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE
 PROTECTED.
 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL
 AIR
 TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO
 HAVE A FIRE
 RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE
 REQUIRED TO
 BE PROTECTED.
  
 PLEASE REVIEW AND PROVIDE CLARIFICATIONS OR INDICATE
 NEW ONES.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL