| Plan Review Notes For Permit 21100549 |
| Permit Number |
21100549 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-15 12:09:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE IS AN INDICATION OF A/C DUCT THAT APPEAR TO BE | | | PENETRATING FIRE RATED WALLS A SEVERAL LOCATIONS. | | | | | | THIS ARE NO INDICATIONS THAT THERE ARE EXISTING FIRE | | | DAMPERS AT THESE LOCATIONS, WHETHER A FIRE DAMPER IS | | | REQUIRED, OR NEW ONES WILL BE INSTALLED. | | | | | | PER NFPA 90 A | | | | | | 5.3* PENETRATIONS ? PROTECTION OF OPENINGS. | | | 5.3.1 FIRE-RATED WALLS AND PARTITIONS. | | | 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE | | | AIR | | | DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR | | | PARTITIONS | | | REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR | | | MORE. | | | 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE | | | OTHER | | | OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE | | | PROTECTED. | | | 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL | | | AIR | | | TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO | | | HAVE A FIRE | | | RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE | | | REQUIRED TO | | | BE PROTECTED. | | | | | | PLEASE REVIEW AND PROVIDE CLARIFICATIONS OR INDICATE | | | NEW ONES. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|