| 2021-10-26 16:52:38 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21100496 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IN THE SUBMITTED APPLIANCE PACKAGE THE FAN FOR THE | | | KITCHEN HOOD IS SPEC?D OUT AS A 1000 CFM BLOWER EXHAUST | | | FAN. M.1 INDICATES THAT THE MAX FAN FOR THE HOOD WILL | | | BE 600 CFM. PLEASE CORRECT THE DRAWING AND PROVIDE THE | | | REQUIRED MAKEUP AIR FOR THE KITCHEN HOOD. FBC RES | | | M1503.4 | | | | | | 2) PLEASE LABEL THE MECHANICAL SHEETS ACCORDING TO THE | | | NAME ON THE DRAWINGS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|