| Date |
Text |
| 2021-12-01 08:11:24 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: |
| | |
| | A SEPERATE PERMIT IS REQUIRED FOR THE 2-STORY COTTAGE. |
| | SUBMIT PERMIT APPLICATION TO: [email protected] |
| | ALL PLANS SHALL REMAIN UNDER PERMIT 21100496 (MAIN RES) |
| | |
| | A SEPERATE PERMIT IS REQUIRED FOR THE SITE WALLS. |
| | PROVISO ON PLAN PAGE C1. |
| | |
| | 1. PROVIDE A COPY OF THE MOST RECENT BOUNDRY LINE |
| | SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. THE ADDRESS ON THE SOILS REPORT STATES 210 SUNSET |
| | RD. CORRECT SOILS REPORT AND RE-SUBMIT. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 3. CORRECT GOVERNING CODES TO 2020 FBC 7TH ED ON PLAN |
| | PAGES A200, A201, A202 AND A210. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM |
| | INSULATION. |
| | FBC 107.3.4 FOR THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. |
| | |
| | 5. PROVIDE THE COVER SHEETS FOR THE FOLLOWING PRODUCT |
| | APPROVALS: FL16749 (OUTSWING DOOR), FL14326 (OUTSWING |
| | DOOR), FL24226 (CASEMENT WINDOWS), FL24229 (DH |
| | WINDOWS), FL24230 (CASEMENT WINDOWS) AND FL25570 (PATIO |
| | DOOR). |
| | THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE |
| | VERSION, AND STATUS, FBC R 301. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 6. IDENTIFY THE LOCATION OF THE PROPOSED HURRICANE |
| | FABRIC, NOA20-1102.08. PROVIDE A SCHEDULE OF OPENING |
| | PROTECTIVE DEVICES OR ASSEMBLIES. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 7. REF. DOOR AND WINDOW SCHEDULES FOR THE FOLLOWING |
| | COMMENTS: |
| | PROVIDE ROUGH OPENING FOR EACH LOCATION. |
| | PROVIDE PRODUCT APPROVAL OR NOA NUMBER FOR EACH TYPE OF |
| | DEVICE. |
| | |
| | NOTE: DESIGN PRESSURES LOCATED ON BLDG. ELEVATIONS, |
| | SHEETS A200 & A201. |
| | |
| | 8. REF. PLAN PAGE S8 (CONCRETE STAIRS), PROVIDE THE |
| | FOLLOWING INFORMATION: |
| | R311.7 STAIRWAYS. |
| | R311.7.1 WIDTH. |
| | STAIRWAYS SHALL NOT BE LESS THAN 36 INCHES (914 MM) IN |
| | CLEAR WIDTH AT ALL POINTS ABOVE THE PERMITTED HANDRAIL |
| | HEIGHT AND BELOW THE REQUIRED HEADROOM HEIGHT. |
| | R311.7.5.1 RISERS. |
| | THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM) |
| | R311.7.5.2 TREADS. |
| | THE MINIMUM TREAD DEPTH SHALL BE 10 INCHES (254 MM). |
| | R311.7.6 LANDINGS FOR STAIRWAYS. |
| | THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM |
| | OF EACH STAIRWAY |
| | R311.7.8 HANDRAILS. |
| | HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF |
| | EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR |
| | MORE RISERS. |
| | R312.1.3 OPENING LIMITATIONS. |
| | R311.7.9 ILLUMINATION. |
| | ALL STAIRS SHALL BE PROVIDED WITH ILLUMINATION IN |
| | ACCORDANCE WITH SECTION R303.6. |
| | SECTION R312 GUARDS AND WINDOW FALL PROTECTION |
| | GUARDS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| | R312.1.1 THROUGH R312.1.4. |
| | R312.1.1 WHERE REQUIRED. R312.1 GUARDS. |
| | FBCR312.1.1 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED |
| | WALKING SURFACES, INCLUDING STAIRS, RAMPS AND LANDINGS, |
| | THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED |
| | VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT |
| | WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF |
| | THE OPEN SIDE. INSECT SCREENING SHALL NOT BE CONSIDERED |
| | AS A GUARD. |
| | R312.1.2 HEIGHT. |
| | REQUIRED GUARDS AT OPEN-SIDED WALKING SURFACES, |
| | INCLUDING STAIRS, PORCHES, BALCONIES OR LANDINGS, SHALL |
| | BE NOT LESS THAN 36 INCHES (914 MM) HIGH |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |