Plan Review Notes
Plan Review Notes For Permit 21100496
Permit Number 21100496
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-01 08:11:24BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 A SEPERATE PERMIT IS REQUIRED FOR THE 2-STORY COTTAGE.
 SUBMIT PERMIT APPLICATION TO: [email protected]
 ALL PLANS SHALL REMAIN UNDER PERMIT 21100496 (MAIN RES)
  
 A SEPERATE PERMIT IS REQUIRED FOR THE SITE WALLS.
 PROVISO ON PLAN PAGE C1.
  
 1. PROVIDE A COPY OF THE MOST RECENT BOUNDRY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. THE ADDRESS ON THE SOILS REPORT STATES 210 SUNSET
 RD. CORRECT SOILS REPORT AND RE-SUBMIT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. CORRECT GOVERNING CODES TO 2020 FBC 7TH ED ON PLAN
 PAGES A200, A201, A202 AND A210.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE THE ICC-ES REPORT FOR THE SPRAY FOAM
 INSULATION.
 FBC 107.3.4 FOR THOSE PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 5. PROVIDE THE COVER SHEETS FOR THE FOLLOWING PRODUCT
 APPROVALS: FL16749 (OUTSWING DOOR), FL14326 (OUTSWING
 DOOR), FL24226 (CASEMENT WINDOWS), FL24229 (DH
 WINDOWS), FL24230 (CASEMENT WINDOWS) AND FL25570 (PATIO
 DOOR).
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6. IDENTIFY THE LOCATION OF THE PROPOSED HURRICANE
 FABRIC, NOA20-1102.08. PROVIDE A SCHEDULE OF OPENING
 PROTECTIVE DEVICES OR ASSEMBLIES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. REF. DOOR AND WINDOW SCHEDULES FOR THE FOLLOWING
 COMMENTS:
 PROVIDE ROUGH OPENING FOR EACH LOCATION.
 PROVIDE PRODUCT APPROVAL OR NOA NUMBER FOR EACH TYPE OF
 DEVICE.
  
 NOTE: DESIGN PRESSURES LOCATED ON BLDG. ELEVATIONS,
 SHEETS A200 & A201.
  
 8. REF. PLAN PAGE S8 (CONCRETE STAIRS), PROVIDE THE
 FOLLOWING INFORMATION:
 R311.7 STAIRWAYS.
 R311.7.1 WIDTH.
 STAIRWAYS SHALL NOT BE LESS THAN 36 INCHES (914 MM) IN
 CLEAR WIDTH AT ALL POINTS ABOVE THE PERMITTED HANDRAIL
 HEIGHT AND BELOW THE REQUIRED HEADROOM HEIGHT.
 R311.7.5.1 RISERS.
 THE MAXIMUM RISER HEIGHT SHALL BE 73/4 INCHES (196 MM)
 R311.7.5.2 TREADS.
 THE MINIMUM TREAD DEPTH SHALL BE 10 INCHES (254 MM).
 R311.7.6 LANDINGS FOR STAIRWAYS.
 THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM
 OF EACH STAIRWAY
 R311.7.8 HANDRAILS.
 HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF
 EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR
 MORE RISERS.
 R312.1.3 OPENING LIMITATIONS.
 R311.7.9 ILLUMINATION.
 ALL STAIRS SHALL BE PROVIDED WITH ILLUMINATION IN
 ACCORDANCE WITH SECTION R303.6.
 SECTION R312 GUARDS AND WINDOW FALL PROTECTION
 GUARDS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 R312.1.1 THROUGH R312.1.4.
 R312.1.1 WHERE REQUIRED. R312.1 GUARDS.
 FBCR312.1.1 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED
 WALKING SURFACES, INCLUDING STAIRS, RAMPS AND LANDINGS,
 THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED
 VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT
 WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF
 THE OPEN SIDE. INSECT SCREENING SHALL NOT BE CONSIDERED
 AS A GUARD.
 R312.1.2 HEIGHT.
 REQUIRED GUARDS AT OPEN-SIDED WALKING SURFACES,
 INCLUDING STAIRS, PORCHES, BALCONIES OR LANDINGS, SHALL
 BE NOT LESS THAN 36 INCHES (914 MM) HIGH
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  