| Plan Review Notes For Permit 21100421 |
| Permit Number |
21100421 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-15 08:57:24 | RAILING - SUBMITTAL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) DRAWING "SD-7" - THE TOP HAND RAIL EXTENSION DOES | | | NOT SHOW A 12 INCH HORIZONTAL EXTENSION - THE EXTENSION | | | SHOWN DIVES DOWN BEFORE IT REACHES THE REQUIRED 12 | | | INCHES - FBC 1014.6 HANDRAIL EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | | BEYOND THE TOP RISER | | | |
|