2021-11-10 15:13:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21100386
 11/10/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT MANUFACTURER?S SPECIFICATIONS AND THE
 INSTALLATION MANUAL. THE SCHEDULE SHALL INDICATE THE
 TYPE OF WATER HEATER- GAS OR ELECTRIC, TANK OR
 TANKLESS, GALLON SIZE FOR TANK, AND THE EFFICIENCY
 RATING BASED ON TABLE C404.2 FBC EC.
  
 2) P101: PLEASE PLACE A NOTE ON THE PLAN INDICATING THE
 PLUMBING STACK REPLACEMENTS WILL BE DONE UNDER SEPARATE
 PERMIT- SECTION 105.1 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  