| 2023-05-01 11:12:35 | NFIP REVIEW APPROVED WITH PROVISO: | | | 1- REVISE "CONSTRUCTION DRAWINGS" ELEVATION | | | CERTIFICATE: | | | A) THE LATITUDE SPECIFIED ON ITEM A5 NEED TO PROVIDE AT | | | LEAST 5 DECIMAL PLACES OR BETTER AS REQUIRED BY THEE | | | FEMA ELEVATION CERTIFICATE PUBLISHED INSTRUCTIONS. | | | B)GARAGE SQUARE FOOTAGE DOESN'T MATCH PLANS. | | | C)REVISE TOTAL NET AREA OF FLOOD OPENINGS TO MATCH | | | PLANS AND PRODUCT APPROVAL. | | | D)THE BASE FLOOD ELEVATION SPECIFIED ON ITEM B9 IS | | | INCORRECT. | | | E)ATTACHED GARAGE ELEVATION SPECIFIED ON ITEM C2(D) TO | | | MATCH PLANS ENGINEER OF RECORD PLANS. | | | F)LOWEST ADJACENT (FINISHED) GRADE AND HIGHEST ADJACENT | | | (FINISHED) GRADE ARE NO SHOWN ON SURVEY WITH PROPOSED | | | STRUCTURE. UNABLE TO VERIFY. | | | G)SURVEYOR NEEDS TO DATE ELEVATION CERTIFICATE WITH | | | CURRENT DATE. ELEVATION CERTIFICATE WAS REVISED BUT | | | SAME DATE WAS SHOWN. | | | |
|