Plan Review Notes
Plan Review Notes For Permit 21100379
Permit Number 21100379
Review Stop NFIP
Sequence Number 4
Notes
Date Text
2022-10-26 18:25:45NFIP REVIEW COMMENTS:
  
 PREVIOUS COMMENT:
 THIRD REVIEW:
 NEED TO SUBMIT CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE AND SURVEY FOR REVIEW.
  
 RESPONSE:
 A) SURVEY SUBMITTED IS FOR THE OLD HOUSE AND GARAGE.
 NEED SURVEY WITH PROPOSED CONSTRUCTION IN ORDER TO
 REVIEW ELEVATION CERTIFICATE SUBMITTED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 B)ELEVATION CERTIFICATE SUBMITTED:
 (1) BUILDING OWNER'S NAME IS INCORRECT. REVISE AS
 REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (2)PROPERTY LEGAL DESCRIPTION DOESN'T MATCH INFORMATION
 SHOWN ON THE SURVEY SUBMITTED. REVISE AS REQUIRED TO
 MATCH.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (3)BUILDING DIAGRAM NUMBER ON ITEM A7 IS INCORRECT.
 REVISE AS REQUIRED. SEE FEMA ELEVATION CERTIFICATE
 INSTRUCTIONS AND REVISE AS REQUIRED. IT LOOKS LIKE THIS
 IS DIAGRAM NUMBER 1B NOT 7.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (4)THE TOTAL NET AREA OF FLOOD OPENING IN ITEM A9(C) IS
 INCORRECT. SEE PLANS AND FLOOD VENT PRODUCT APPROVAL
 AND REVISE AS REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (5)THE BASE FLOOD ELEVATION SPECIFIED ON ITEM B9 IS
 INCORRECT. SEE FLOOD INSURANCE RATE MAP (FIRM) AND
 REVISE AS REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (6)TOP OF BOTTOM FLOOR ELEVATION SPECIFIED ON ITEM
 C2(A) IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (7)ATTACHED GARAGE ELEVATION SPECIFIED ON ITEM C2(D) IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED.
 SEC.107.2.1 CITY AMENDMENTS.
  
 (8)LOWEST ELEVATION OF AIR CONDITIONING UNIT SPECIFIED
 ON ITEM C2(E) DOESN'T COMPLY WITH CITY ORDINANCE
 4729-17.ELEVATION OF EQUIPMENT NEEDS TO BE 2 FEET ABOVE
 THE BASE FLOOD ELEVATION (9'-0" MIN.). COORDINATE WITH
 ENGINEER OF RECORD AND REVISE AS REQUIRED.
  
 (9) LOWEST ADJACENT (FINISHED) GRADE AND HIGHEST
 ADJACENT (FINISHED) GRADE WILL BE REVIEWED ONCE REVISED
 SURVEY WITH PROPOSED CONSTRUCTION IS SUBMITTED.
  
 CITY ORDINANCE 4729-17.
 SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE.
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]