| 2022-10-26 18:25:45 | NFIP REVIEW COMMENTS: |
| | |
| | PREVIOUS COMMENT: |
| | THIRD REVIEW: |
| | NEED TO SUBMIT CONSTRUCTION DRAWINGS ELEVATION |
| | CERTIFICATE AND SURVEY FOR REVIEW. |
| | |
| | RESPONSE: |
| | A) SURVEY SUBMITTED IS FOR THE OLD HOUSE AND GARAGE. |
| | NEED SURVEY WITH PROPOSED CONSTRUCTION IN ORDER TO |
| | REVIEW ELEVATION CERTIFICATE SUBMITTED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | B)ELEVATION CERTIFICATE SUBMITTED: |
| | (1) BUILDING OWNER'S NAME IS INCORRECT. REVISE AS |
| | REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (2)PROPERTY LEGAL DESCRIPTION DOESN'T MATCH INFORMATION |
| | SHOWN ON THE SURVEY SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (3)BUILDING DIAGRAM NUMBER ON ITEM A7 IS INCORRECT. |
| | REVISE AS REQUIRED. SEE FEMA ELEVATION CERTIFICATE |
| | INSTRUCTIONS AND REVISE AS REQUIRED. IT LOOKS LIKE THIS |
| | IS DIAGRAM NUMBER 1B NOT 7. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (4)THE TOTAL NET AREA OF FLOOD OPENING IN ITEM A9(C) IS |
| | INCORRECT. SEE PLANS AND FLOOD VENT PRODUCT APPROVAL |
| | AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (5)THE BASE FLOOD ELEVATION SPECIFIED ON ITEM B9 IS |
| | INCORRECT. SEE FLOOD INSURANCE RATE MAP (FIRM) AND |
| | REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (6)TOP OF BOTTOM FLOOR ELEVATION SPECIFIED ON ITEM |
| | C2(A) IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (7)ATTACHED GARAGE ELEVATION SPECIFIED ON ITEM C2(D) IS |
| | INCORRECT. SEE PLANS AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (8)LOWEST ELEVATION OF AIR CONDITIONING UNIT SPECIFIED |
| | ON ITEM C2(E) DOESN'T COMPLY WITH CITY ORDINANCE |
| | 4729-17.ELEVATION OF EQUIPMENT NEEDS TO BE 2 FEET ABOVE |
| | THE BASE FLOOD ELEVATION (9'-0" MIN.). COORDINATE WITH |
| | ENGINEER OF RECORD AND REVISE AS REQUIRED. |
| | |
| | (9) LOWEST ADJACENT (FINISHED) GRADE AND HIGHEST |
| | ADJACENT (FINISHED) GRADE WILL BE REVIEWED ONCE REVISED |
| | SURVEY WITH PROPOSED CONSTRUCTION IS SUBMITTED. |
| | |
| | CITY ORDINANCE 4729-17. |
| | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING |
| | CODE. |
| | SEC. 107.3.5.3 CITY AMENDMENTS. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT |
| | FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED: |
| | A) CONSTRUCTION DRAWINGS. |
| | B) BUILDING UNDER CONSTRUCTION. |
| | C) FINISHED CONSTRUCTION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |