| Date |
Text |
| 2022-10-26 18:19:50 | RESIDENTIAL (R3) ADDITION, ALTERATION 4TH BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21100379 |
| | 102 GREGORY RD |
| | |
| | PREVIOUS COMMENT: |
| | 1- REPEAT COMMENT. THREE TIMES. NOT ADDRESSED AT ALL. |
| | NEED TO SUBMIT CONSTRUCTION DRAWINGS ELEVATION |
| | CERTIFICATE AND SURVEY FOR REVIEW. |
| | |
| | RESPONSE: |
| | A) SURVEY SUBMITTED IS FOR THE OLD HOUSE AND GARAGE. |
| | NEED SURVEY WITH PROPOSED CONSTRUCTION IN ORDER TO |
| | REVIEW ELEVATION CERTIFICATE SUBMITTED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | B)ELEVATION CERTIFICATE SUBMITTED: |
| | (1) BUILDING OWNER'S NAME IS INCORRECT. REVISE AS |
| | REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (2)PROPERTY LEGAL DESCRIPTION DOESN'T MATCH INFORMATION |
| | SHOWN ON THE SURVEY SUBMITTED. REVISE AS REQUIRED TO |
| | MATCH. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (3)BUILDING DIAGRAM NUMBER ON ITEM A7 IS INCORRECT. |
| | REVISE AS REQUIRED. SEE FEMA ELEVATION CERTIFICATE |
| | INSTRUCTIONS AND REVISE AS REQUIRED. IT LOOKS LIKE THIS |
| | IS DIAGRAM NUMBER 1B NOT 7. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (4)THE TOTAL NET AREA OF FLOOD OPENING IN ITEM A9(C) IS |
| | INCORRECT. SEE PLANS AND FLOOD VENT PRODUCT APPROVAL |
| | AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (5)THE BASE FLOOD ELEVATION SPECIFIED ON ITEM B9 IS |
| | INCORRECT. SEE FLOOD INSURANCE RATE MAP (FIRM) AND |
| | REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (6)TOP OF BOTTOM FLOOR ELEVATION SPECIFIED ON ITEM |
| | C2(A) IS INCORRECT. SEE PLANS AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (7)ATTACHED GARAGE ELEVATION SPECIFIED ON ITEM C2(D) IS |
| | INCORRECT. SEE PLANS AND REVISE AS REQUIRED. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | (8)LOWEST ELEVATION OF AIR CONDITIONING UNIT SPECIFIED |
| | ON ITEM C2(E) DOESN'T COMPLY WITH CITY ORDINANCE |
| | 4729-17.ELEVATION OF EQUIPMENT NEEDS TO BE 2 FEET ABOVE |
| | THE BASE FLOOD ELEVATION (9'-0" MIN.). COORDINATE WITH |
| | ENGINEER OF RECORD AND REVISE AS REQUIRED. |
| | |
| | (9) LOWEST ADJACENT (FINISHED) GRADE AND HIGHEST |
| | ADJACENT (FINISHED) GRADE WILL BE REVIEWED ONCE REVISED |
| | SURVEY WITH PROPOSED CONSTRUCTION IS SUBMITTED. |
| | |
| | |
| | PREVIOUS COMMENT: |
| | 2- DRAINAGE PLAN SUBMITTED IS FOR THE EXISTING |
| | STRUCTURES. NEED TO PROVIDE DRAINAGE PLAN WITH PROPOSED |
| | STRUCTURES. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | PREVIOUS COMMENT: |
| | 15- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR |
| | LATER AS A DEFERRED SUBMITTAL). |
| | |
| | A)INSWING ENTRY DOORS A SHOWN ON PLANS. |
| | B)INSWING SIDE DOOR #4 AS SHOWN ON PLANS. |
| | C)SLIDING GLASS DOORS (NOTE: NEED FOR LARGE MISSILE |
| | IMPACT) |
| | D)OVERHEAD GARAGE DOOR. |
| | E)CASEMENT WINDOWS. |
| | F)SINGLE HUNG WINDOWS. |
| | G)FIXED WINDOWS. |
| | H)HORIZONTAL ROLLER |
| | WINDOWS. |
| | I)WINDOW MULLIONS (NOTE: NEED TO SPECIFY |
| | MULLION SIZE TO AVOID DELAYS/CONFLICTS). |
| | J)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT |
| | GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | K)SHINGLES. |
| | L)PEEL & STICK SHINGLES UNDERLAYMENT SPECIFIED ON |
| | PLANS. |
| | M)RIDGE VENTS AS SPECIFIED ON PLANS. |
| | N)FLOOD VENTS AS SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | ACCORDING TO ENGINEER OF RECORD RESPONSE LETTER ALL |
| | PRODUCT APPROVALS WILL BE APPROVED AND WILL BE |
| | SUBMITTED LATER AS DEFERRED SUBMITTALS. |
| | ONLY SOME PRODUCT APPROVALS WERE SUBMITTED AT THIS TIME |
| | AND THEY WERE NOT REVIEWED/APPROVED BY THE DESIGNER OF |
| | RECORD. ALSO, THE FLOOD VENT PRODUCT APPROVAL SUBMITTED |
| | IS INCOMPLETE. IT NEEDS THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND INSTALLATION INSTRUCTIONS. TO SAVE TIME, |
| | ALL PRODUCT APPROVALS SUBMITTED THIS TIME WILL BE |
| | BLOCKED AND WILL NOT BE REVIEWED AT THIS TIME. |
| | CONTRACTOR TO ADVISE IF SUBMITTING ALL THE PRODUCT |
| | APPROVALS (COMPLETE REPORTS) LATER AS A DEFERRED |
| | SUBMITTAL ONCE THEY ARE APPROVED BY THE DESIGNER OF |
| | RECORD OR IF SUBMITTING THEM ON NEXT RESUBMITTAL. |
| | |
| | NEW COMMENT BASED ON REVISED PLANS: |
| | 16- SHEET A-2: ENGINEER REVISED THE BASE FLOOD |
| | ELEVATION UNDER FLOOD ZONE. THE REVISED INFORMATION IS |
| | INCORRECT. ACCORDING TO FLOOD INSURANCE RATE MAP (FIRM) |
| | DATED 10-05-2017 THE BASE FLOOD ELEVATION IS 7'-0" NOT |
| | 6'-0". REVISE AS REQUIRED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |