2022-07-19 13:00:32RESIDENTIAL (R3) ADDITION, ALTERATION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100379
  
 PREVIOUS COMMENT:
 1- NFIP COMMENTS WILL RESOLVE THIS COMMENT.
  NOTE: DURING THE PERMITTING OF THIS STRUCTURE THREE
 DIFFERENT
  FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
  A) CONSTRUCTION DRAWINGS.
  B) BUILDING UNDER CONSTRUCTION.
  C) FINISHED CONSTRUCTION.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NOT ADDRESSED AT ALL. NEED
 TO SUBMIT CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE
 AND SURVEY FOR REVIEW.
  
 PREVIOUS COMMENT:
 2- LOT DRAINAGE
 2ND REVIEW NO DRAINAGE PLAN WAS ADDED. PLEASE ADD
 DRAWING OR NOTES TO SATISFY DRAINAGE
  PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
  FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
  AMENDMENTS. SEC. 110.9 CITY AMENDMENTS. NOTE:
 DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED GRADE
 ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
  ADJACENT PROPERTIES.
  
 RESPONSE:
 DRAINAGE PLAN SUBMITTED IS FOR THE EXISTING STRUCTURES.
 NEED TO PROVIDE DRAINAGE PLAN WITH PROPOSED STRUCTURES.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 PREVIOUS COMMENT:
 15- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001
  FOR (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
  SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
  PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
  PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
  DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  A)INSWING ENTRY DOORS A SHOWN ON PLANS.
  B)INSWING SIDE DOOR #4 AS SHOWN ON PLANS.
  C)SLIDING GLASS DOORS (NOTE: NEED FOR LARGE MISSILE
 IMPACT)
  D)OVERHEAD GARAGE DOOR.
  E)CASEMENT WINDOWS.
  F)SINGLE HUNG WINDOWS.
  G)FIXED WINDOWS.
  H)HORIZONTAL ROLLER
  WINDOWS.
  I)WINDOW MULLIONS (NOTE: NEED TO SPECIFY
  MULLION SIZE TO AVOID DELAYS/CONFLICTS).
  J)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT
  GLAZING. AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
  K)SHINGLES.
  L)PEEL & STICK SHINGLES UNDERLAYMENT SPECIFIED ON
 PLANS.
  M)RIDGE VENTS AS SPECIFIED ON PLANS.
  N)FLOOD VENTS AS SPECIFIED ON PLANS.
  
 RESPONSE:
 ACCORDING TO ENGINEER OF RECORD RESPONSE LETTER ALL
 PRODUCT APPROVALS WILL BE APPROVED AND WILL BE
 SUBMITTED LATER AS DEFERRED SUBMITTALS.
  
  WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
  ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
  THE REVISION MADE, IDENTIFYING THE SHEET OR
  SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
  HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
  ANTICIPATED COOPERATION.
  
  PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
  QUESTIONS REGARDING THESE COMMENTS,
  JULIO GOMEZ
  COMMERCIAL COMBINATION PLANS EXAMINER
  DEVELOPMENT SERVICES DEPARTMENT
  BUILDING DIVISION
  (561)805-6712