| Plan Review Notes For Permit 21100360 |
| Permit Number |
21100360 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-05 17:05:50 | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1: | | | | | | 1.) THE MARKED UP PRODUCT APPROVALS DO NOT MATCH THE | | | LAYOUT AND THE SCHEDULE FOR OPENING PROTECTIVE DEVICES. | | | PLEASE CORRECT THE MARK UPS WITHIN THE PRODUCT | | | APPROVALS TO MATCH THE LAYOUT AND SCHEDULE. | | | | | | 2.) PLEASE PROVIDE AN ELECTRIC PERMIT FOR ELECTRIC WORK | | | INCLUDING INSTALLATION OF WIRING & DISCONNECTS. |
|