Plan Review Notes
Plan Review Notes For Permit 21100347
Permit Number 21100347
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-02 08:53:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21100347 5670 CORPORATE WAY # 13
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS OR
 OTHER ITEMS NOTED ON ARCHITECTURAL PLANS MUST BE
 SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT, NOT
 THE FIXTURE RIM. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION PER FBC ACC 604.4.
  
 2.PER WPB FBC 107.2.1, PROVIDE FINISH WALL SCHEDULE FOR
 REMODELED BATHROOM AND FOR JANITOR SINK CLOSET. REFER
 TO FBC PL 310.3 AND FBC 1210.2.2. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. PLEASE NOTE
 THAT FBC 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 3.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 4.PER FBC PL 909.1, PROVIDE A VENT FOR THE WATER
 CLOSET. PLEASE NOTE THAT IF PROVIDING A WET VENT FOR
 THE WATER CLOSET, PER FBC PL 912.1, ONLY THE LAVATORY
 MAY BE INSTALLED ON THE WET VENT. IF INDIVIDUALLY VENT
 IN ACCORDANCE WITH FBC PL 910.1. THE VENT MUST RISE
 VERTICALLY ABOVE THE CENTERLINE OF THE DRAIN TO A POINT
 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE WATER CLOSET
 PER FBC PL 905.3 AND 905.4.
  
 5.RE: P0.1/WATER HEATER DETAIL: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING
 ?A) SPECIFICATION FOR THE EXPANSION VALVE (LEAD FREE)
 ?B) DIRECTION FOR EXPANSION VALVE DISCHARGE INCLUDING
 TERMINATION.
 ?C) SPECIFIC DIRECTION FOR RELIEF VALVE DISCHARGE AND
 PAN DRAIN (INCLUDING TERMINATION); COMPLY WITH FBC PL
 504.6(1-14) AND 504.7.2. PLEASE NOTE THAT A WASTE
 RECEPTOR BY DEFINITION (FBC PL SECTION 202) IS A FLOOR
 SINK, STANDPIPE, HUB DRAIN OR FLOOR DRAIN THAT RECEIVES
 THE DISCHARGE OF ONE OR MORE INDIRECT WASTE PIPES. A
 MOP BASIN DOES NOT FIT THIS DESCRIPTION.
  
 6.IT IS NOTED THAT THE HOT WATER TO THE BREAK ROOM SINK
 HAS AN ISOLATION VALVE IN THE LINE. THIS IS A
 RECIRCULATED LINE WHICH WILL NOT FUNCTION IF THE
 ISOLATION VALVE IS CLOSED. PLEASE NOTE THAT THE
 REQUIREMENT FOR A FULL OPEN VALVE AS NOTED IN FBC PL
 606.1(5) IS NOT APPLICABLE AS WPB BUILDING FOLLOWS THE
 INTERPRETATION OF IBC PLUMBING COMMENTARY 606.1(5)
 WHICH STATES A WATER PIPE EXTENDING VERTICALLY THROUGH
 ONE OR MORE FLOORS AND CONVEYING WATER VERTICALLY
 DOWNWARD IS CONSIDERED A DOWN-FEED. VALVES AT THE TOP
 OF DOWN-FEEDS ARE HELPFUL FOR SERVICING MULTI-STORY
 BUILDING SO THAT ONLY SMALL AREAS OF THE BUILDING WILL
 BE WITHOUT WATER TO FACILITATE REPAIRS IN ONE AREA.
  
 7.PER WPB FBC 107.2.1, INDICATE HOW THE PLUMBING FOR
 THE TOILET ROOM THAT IS NOT BEING REMODELED IS
 INTEGRATED WITH THE NEW WORK.
 ?A) DOES EXISTING SANITARY TIE INTO NEW SANITARY
 (INDICATE POINTS OF CONNECTION) OR THE OTHER WAY AROUND
 OR SEPARATE TO BUILDING SEWER
 ?B) DOES EXISTING WATER (HOT AND COLD) CONNECT TO NEW
 (INDICATE POINTS OF CONNECTION) OR THE OTHER WAY AROUND
 OR SEPARATE TO WATER MAIN.
 ?C) EXISTING BACKFLOW PREVENTER, NEW BACKFLOW
 PREVENTER? PROVIDE NOTE. SPECIFY AND PROVIDE DETAIL IF
 APPLICABLE
  
 7.RE: P2.0/KEY NOTE 1; PER WPB FBC 107.2.1, AMEND NOTE
 TO STATE NEW TOILET TO BE LOCATED AS REQUIRED BY
 FLORIDA ACCESSIBILITY CODE 604.2
  
 8.RE: P3.0/KEY NOTE 1; PER WPB FBC 107.2.1, AMEND NOTE
 TO STATE NEW TOILET TO BE LOCATED AS REQUIRED BY
 FLORIDA ACCESSIBILITY CODE 604.2
  
 9.AC CONDENSATE APPEARS TO BE EXISTING ACCORDING TO
 M0.1/SPECIAL NOTE TO HVAC CONTRACTOR. P0.1 PROVIDES
 DETAIL FOR A CONDENSATE DRY WELL, A CONDENSATE PUMP IS
 SCHEDULED AND THERE ARE MATERIAL SPECIFICATIONS. PER
 WPB FBC 107.2.1, PLEASE CLARIFY.
  
 10.PER WPB FBC 107.2.1, SCHEDULE AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 419.5 FOR THE
 SCHEDULED ADA LAVATORY AND PROVIDE A DETAIL FOR THE
 SAME.
  
 11.PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE WITH
 DFU AND DRAIN SIZE/WSFU AND CONNECTION SIZE
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21100347 5670 CORPORATE WAY # 13
  