| 2021-10-19 06:30:18 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21100347 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M 2.1: PLEASE PROVIDE DUCT SIZES FOR ALL |
| | DUCTWORK IN THIS PROJECT. |
| | |
| | 2) SHEET A120 INDICATES A 1 HR TENANT SEPARATION WALL |
| | AT THE SOUTH END OF THIS BUILDING BUT SHEET M 2.1 |
| | INDICATES A 12 X 12 O/A INTAKE LOCATED IN THE OTHER |
| | TENANT?S SPACE. PLEASE SHOW THIS O/A INTAKE GOING TO |
| | THE EXTERIOR OF THE BUILDING AND PROVIDE A FIRE DAMPER |
| | AT THE PENETRATION OF THIS DUCT AT THE 1 HR RATED WALL. |
| | FBC M 403.2.1, 607 |
| | |
| | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE IN THIS TENANT SPACE ACCORDING TO FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 4) PLEASE SHOW THAT THE BATHROOM EXHAUST MEETS THE 10 |
| | FT. DISTANCE FROM THE EXTERIOR BREAK ROOM ENTRY DOOR. |
| | FBC M 501.3.1 |
| | |
| | 5) PLEASE SHOW THE BATH EXHAUST TERMINATION LOCATION |
| | FOR RESTROOM 119. FBC M 501.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |