Plan Review Notes
Plan Review Notes For Permit 21100339
Permit Number 21100339
Review Stop M
Sequence Number 2
Notes
Date Text
2021-11-19 14:24:01BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1 THE
 OUTDOOR AIR FOR CONFERENCE ROOM 1 SHOUD BE 111 CFM.
 OUTDOOR AIR FOR CONFERENCE ROOM 2 SHOULD BE 62 CFM'S
 AND OUTDOOR AIR FOR THE RECEPTION AREA SHOULD BE 97
 CFM'S.
  