| Plan Review Notes For Permit 21100339 |
| Permit Number |
21100339 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-11-19 14:24:01 | BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1 THE | | | OUTDOOR AIR FOR CONFERENCE ROOM 1 SHOUD BE 111 CFM. | | | OUTDOOR AIR FOR CONFERENCE ROOM 2 SHOULD BE 62 CFM'S | | | AND OUTDOOR AIR FOR THE RECEPTION AREA SHOULD BE 97 | | | CFM'S. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|