| 2022-04-21 07:55:10 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NEW SURVEY THAT WAS SUBMITTED, WITH THE | | | GENERATOR EXHAUST 10' FROM OPENINGS INTO A BUILDING | | | NOTE. HAS THE GENERATOR DRAWN INSIDE THE DWELLING. | | | SUBMIT A CORRECTED SURVEY. FBC 107.2.1 & FBC-R303.5 |
|