Plan Review Notes
Plan Review Notes For Permit 21100336
Permit Number 21100336
Review Stop B
Sequence Number 2
Notes
Date Text
2022-03-14 08:31:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) NOT RESOLVED. [ THE ENGINEER'S DIGITAL SIGNATURE
 COULD NOT BE RESOLVED. SEE SIGNATURE REVIEW. ] SUBMIT
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE
 PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2
  
 3) NOT RESOLVED, [ I DID NOT SEE THE NOTE ON THE
 SURVEY. ] NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST
 IS REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A
 BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  