| Plan Review Notes For Permit 21100336 |
| Permit Number |
21100336 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-03-14 08:31:41 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) RESOLVED. | | | | | | 2) NOT RESOLVED. [ THE ENGINEER'S DIGITAL SIGNATURE | | | COULD NOT BE RESOLVED. SEE SIGNATURE REVIEW. ] SUBMIT | | | SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE | | | PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2 | | | | | | 3) NOT RESOLVED, [ I DID NOT SEE THE NOTE ON THE | | | SURVEY. ] NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST | | | IS REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A | | | BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|