| 2021-10-19 19:44:37 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21100336 |
| | 10/19/21 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ADDRESS ON PERMIT APPLICATIONS IS INCORRECT ACTUAL |
| | ADDRESS IS 6098 WILDCAT RUN. PLEASE SUBMIT NEW PERMIT |
| | APPLICATIONS TO REFLECT THE ACTUAL PROPERTY ADDRESS |
| | WHERE THE WORK IS GOING TO BE PERFORMED.WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | 2) THE GAS REVIEW IS BEING DONE UNDER PERMIT #21100573 |
| | 3) THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) |
| | FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, |
| | EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS |
| | OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION |
| | INSTRUCTIONS. |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |