| Notes |
| Date |
Text |
| 2021-11-17 09:49:42 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | GENERATOR. FBC 107.2.1 | | | | | | 2) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING | | | FOR THE PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2 | | | | | | 3) NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST IS | | | REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A | | | BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|