| 2021-12-03 07:41:51 | PLANS FOR THIS PROJECT ARE WITH PERMIT 21081320 |
| | |
| | PLEASE RESPOND TO 2ND CYCLE REVIEW COMMENTS BELOW. |
| | |
| | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21081320 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS |
| | MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE |
| | PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE |
| | AND A CABANA-ACCESSORY STRUCTURE. |
| | |
| | 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A |
| | CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE |
| | PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A |
| | RESCHECK FOR EACH STRUCTURE SEPARATELY. |
| | |
| | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY |
| | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION |
| | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |