| 2021-11-29 14:59:13 | NFIP PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 3RD REVIEW |
| | |
| | RE: FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | BASED ON OUR INTERNAL REVIEW OF THIS ELEVATION |
| | CERTIFICATE, THE FOLLOWING CORRECTIONS ARE REQUIRED. |
| | |
| | |
| | 1. SECTION C2 A) OF THE EC STATES TOP OF BOTTOM FLOOR |
| | IS 9.0FT NAVD. (DFE IS 9.0FT). |
| | BOUNDARY LINE SURVEY STATES THRESHOLD EL.=8.98 FOR THE |
| | GROUND FLOOR. PLEASE CORRECT. |
| | |
| | THERE IS A DIFFERENCE OF 0.02 BETWEEN SECTION C2 A) |
| | (9.0) OF THE EC AND THRESHOLD EL.=8.98 ON THE BOUNDARY |
| | LINE SURVEY. |
| | IF THE INSTALLATION OF FLOORING WILL BRING THE FINISHED |
| | FLOOR ELEVATION TO 10.0'. AS REQUIRED, PLACE A NOTE IN |
| | SECTION D, COMMENTS. |
| | PROVIDE CLARIFICATION ON THE WORD "THRESHOLD" ON THE |
| | SURVEY. EITHER REMOVE IT FROM SURVEY OR PROVIDE |
| | CLARIFICATION IN THE COMMENTS SECTION. |
| | |
| | |
| | 2. SECTION C2 E) STATES LOWEST ELEVATION OF EQUIPMENT |
| | IS 9.0 NAVD. (DFE IS 9.0). CORRECT. |
| | COMMENT IN SECTION D STATES THE BOTTOM OF THE ELEVATOR |
| | SHAFT IS 5 BELOW C2 (A). WE COULD NOT VERIFY IF |
| | EQUIPMENT IS MOUNTED AT THIS LEVEL. |
| | |
| | SECTION C2 E) AND THE COMMENT ON ELEVATOR EQUIPMENT IN |
| | SECTION D ARE IN CONFLICT. REMOVE THE NOTE REFERENCING |
| | THE ELEVATOR EQUIPMENT AND ESTABLISH THE ELEVATION OF |
| | THE ELEVATOR EQUIPMENT. (ELEVATOR EQUIPMENT IS ON THE |
| | GROUND FLOOR BEHIND THE ELEVATOR SHAFT. |
| | SEE ELECTRICAL PLAN PAGE E-1). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |