| 2021-12-21 16:11:32 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21100182 |
| | ADD: 300 S. AUSTRALIAN AVE. # 512 |
| | CONT: EMPIRE TODAY |
| | TEL: 888-588-2300 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC. 21ST /2021 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) 2ND REQUEST. CONTRACTOR CREATED PLANS. CERTIFICATION |
| | BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DREW THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. |
| | |
| | 3) PLEASE NOTE THE CITY OF WEST PALM REQUIRES THE |
| | ACTUAL TEST REPORTS FOR THE FINISH FLOOR TO BE |
| | INSTALLED PER THE FINISH FLOOR LVP FLOORING. FLOOR |
| | INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, |
| | MARBLE, VINYL LAMINATE FLOORING AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS (THE SAME |
| | MANUFACTURER) FOR TYPE I AND OR TYPE II BUILDINGS |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 3A) SEMI-COMPLIED. MANUFACTURER WIDGET CO. FBC-B 2020 |
| | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E-492. |
| | |
| | 3B) SEMI-COMPLIED, MANUFACTURER WIDGET CO. FBC-B 2020 |
| | 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 3C) SEMI-COMPLIED. MANUFACTURER: BADGER CORK. BADGER |
| | CORK WAS BOUGHT OUT BY ACOUSTICORK, THE PARENT CO. IS |
| | AMORIM. YOU CAN?T MIX AND MATCH THE PRODUCTS FROM 2 |
| | DIFFERENT MANUFACTURERS. |
| | FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. INSULATION |
| | INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING |
| | WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | LVT & LPT LUXURY VINYL TILE. FLOOR FINISH |
| | CLASSIFICATION AS REQUIRED IN SECTION 804.2 |
| | CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF |
| | THE 2020 FBC-B. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |