Plan Review Notes
Plan Review Notes For Permit 21100162
Permit Number 21100162
Review Stop ENG-P
Sequence Number 3
Notes
Date Text
2022-08-10 14:58:461) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE
 MATERIAL, AND DESCRIPTION ON THE SITE PLAN. CONTACT
 JANICE TARBILL, [email protected] FOR AS-BUILT
 INFORMATION. INCLUDE AS-BUILT INFORMATION IN YOUR
 RESUBMITTAL.
 2) POLE MUST BE 5' AWAY FROM CITY UTILITIES.
 3) VERIFY ADA ACCESSIBILITY IS MAINTAINED ON THE
 SIDEWALK NEXT TO THE POLE LOCATION.
 2) PROVIDE PLAN FOR PROPOSED ELECTRIC ROUT AND PROFILE
 SHOWING ALL CROSSING DATA FOR OTHER UTILITIES.
  