| Plan Review Notes For Permit 21100162 |
| Permit Number |
21100162 |
|
| Review Stop |
ENG-P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-10 14:58:46 | 1) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS. | | | INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE | | | MATERIAL, AND DESCRIPTION ON THE SITE PLAN. CONTACT | | | JANICE TARBILL, [email protected] FOR AS-BUILT | | | INFORMATION. INCLUDE AS-BUILT INFORMATION IN YOUR | | | RESUBMITTAL. | | | 2) POLE MUST BE 5' AWAY FROM CITY UTILITIES. | | | 3) VERIFY ADA ACCESSIBILITY IS MAINTAINED ON THE | | | SIDEWALK NEXT TO THE POLE LOCATION. | | | 2) PROVIDE PLAN FOR PROPOSED ELECTRIC ROUT AND PROFILE | | | SHOWING ALL CROSSING DATA FOR OTHER UTILITIES. | | | | | | SUZANNE BERGLUND | | | [email protected] | | | 561-494-1075 | | | |
|