Plan Review Notes
Plan Review Notes For Permit 21100157
Permit Number 21100157
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-26 07:46:3810/26/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET A-1 AND OR A-10;
  
 A. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A
 PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX
 PER THE 2020 FBC SECTION P 403.2.
  
 B. WOULD YOU PLEASE SHOW A SERVICE SINK (MOP SINK), AND
 THE SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 AND
 2020 FBC SEC. P 310.3. WOULD YOU PLEASE MAKE A NOTE ON
 THIS SHEET?
  
 C. THERE IS A MOP SINK IN FRONT OF THE WATER CLOSER TO
 RESTROOM TWO. WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE SIDEWALL AND 56 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL PER THE 2020 FBC ACC.
 SEC. 604.3.1.
  
 D. WOULD YOU, PLEASE SHOW THE 30 INCHES BY 48 INCHES
 INSIDE THE RUNNING RADIUS PER THE 2020 FBC ACC SEC. 305
 CLEAR FLOOR OR GROUND SPACE.
  
 E. ON SHEET A-10 DETAIL, FOUR SHALL BE INSTALLED
 HORIZONTALLY PER THE 2020 FBC ACC SEC. 609.4. THE
 HORIZONTAL GRAB BARS NEED TO BE MEASURED TO THE CENTER
 OF THE BAR PER THE 2020 FBC ACC SEC. 604.5.1 SIDE WALL
 AND 604.5.2 REAR WALL. THE REFLECTIVE PART OF THE
 MIRROR NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 F. WOULD YOU PLEASE PROVIDE A SLAB REPAIR? SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 2. ON SHEET P-1;
  
 A. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A
 PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX
 PER THE 2020 FBC SECTION P 403.2. WOULD YOU PLEASE DO
 THIS FOR ALL SIMILAR PAGES UNDER ALL TRADES?
  
 B. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF
 FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER
 OF FIXTURES.
  
 C. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 D. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved