| Date |
Text |
| 2021-10-26 07:46:38 | 10/26/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET A-1 AND OR A-10; |
| | |
| | A. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A |
| | PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX |
| | PER THE 2020 FBC SECTION P 403.2. |
| | |
| | B. WOULD YOU PLEASE SHOW A SERVICE SINK (MOP SINK), AND |
| | THE SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN |
| | ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 AND |
| | 2020 FBC SEC. P 310.3. WOULD YOU PLEASE MAKE A NOTE ON |
| | THIS SHEET? |
| | |
| | C. THERE IS A MOP SINK IN FRONT OF THE WATER CLOSER TO |
| | RESTROOM TWO. WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE SIDEWALL AND 56 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL PER THE 2020 FBC ACC. |
| | SEC. 604.3.1. |
| | |
| | D. WOULD YOU, PLEASE SHOW THE 30 INCHES BY 48 INCHES |
| | INSIDE THE RUNNING RADIUS PER THE 2020 FBC ACC SEC. 305 |
| | CLEAR FLOOR OR GROUND SPACE. |
| | |
| | E. ON SHEET A-10 DETAIL, FOUR SHALL BE INSTALLED |
| | HORIZONTALLY PER THE 2020 FBC ACC SEC. 609.4. THE |
| | HORIZONTAL GRAB BARS NEED TO BE MEASURED TO THE CENTER |
| | OF THE BAR PER THE 2020 FBC ACC SEC. 604.5.1 SIDE WALL |
| | AND 604.5.2 REAR WALL. THE REFLECTIVE PART OF THE |
| | MIRROR NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER |
| | THE 2020 FBC ACC SEC. 603.3. |
| | |
| | F. WOULD YOU PLEASE PROVIDE A SLAB REPAIR? SHOW THE |
| | WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| | EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING |
| | OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO |
| | INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| | VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE |
| | CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| | |
| | 2. ON SHEET P-1; |
| | |
| | A. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A |
| | PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX |
| | PER THE 2020 FBC SECTION P 403.2. WOULD YOU PLEASE DO |
| | THIS FOR ALL SIMILAR PAGES UNDER ALL TRADES? |
| | |
| | B. WOULD YOU PLEASE PROVIDE THE MINIMUM NUMBER OF |
| | FIXTURES FOR THE OCCUPANT LOAD BASED ON THE ACTUAL USE |
| | OF THE BUILDING OR SPACE PER TABLE 403.1 MINIMUM NUMBER |
| | OF FIXTURES. |
| | |
| | C. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS. |
| | |
| | D. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |