Plan Review Notes
Plan Review Notes For Permit 21100101
Permit Number 21100101
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-23 14:18:33NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100101
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- LOT DRAINAGE:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: PROPOSED HOUSE FOOTPRINT IS BIGGER THAN EXISTING
 HOUSE. ALSO, PLANS CALL FOR FUTURE POOL EQUIPMENT.
 NEIGHBORS ON THE EAST AND SOUTH SIDES ARE GOING TO BE
 AFFECTED. SITE/DRAINAGE PLAN SUBMITTED DOESN'T SHOW ANY
 GRADE ELEVATIONS. ALSO, DRAINAGE PLAN SUBMITTED DOESN'T
 SHOW HOW TO KEEP THE SURFACE WATER AWAY FROM ADJACENT
 NEIGHBORS. PROVIDE COMPLETE DRAINAGE PLAN WITH GRADE
 ELEVATIONS.
  
 3- SHEET SP-1:
 A)NEED TO SPECIFY THE LIVE AND DEAD LOADS FOR SECOND
 FLOOR TRUSSES. SEC. R301.4 AND SEC. R301.5
 FBC-RESIDENTIAL.
  
 B)SPECIFY ROOF TRUSSES DEAD AND LIVE LOADS. CLEARLY
 SPECIFY TOP AND BOTTOM LOADS. INCLUDING THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 SEE FOOTNOTES "B" AND "G".
  
 4- SHEET A-1:
 A)FIRST FLOOR: SPECIFY SIZE OF ATTIC ACCESS. SEC.
 R807.1 FBC-RESIDENTIAL.
  
 B)SECOND FLOOR: SPECIFY LOCATION AND SIZE OF ATTIC
 ACCESS AT THE MASTER BEDROOM WING AREA AND AT GARAGE
 WING AREA. SEC. R807.1 FBC-RESIDENTIAL.
  
 5- ATTIC ACCESS DETAIL 1/A-4 ON SHEET A-5 SPECIFIES
 21-1/2" CLEAR OPENING. THIS DOESN'T COMPLY WITH SEC.
 R807.1 FBC-RESIDENTIAL. MIN. SIZE IS 22" BY 30" REVISE
 AS REQUIRED.
  
 6- SHEET A-4:
 A)TWO STORY WALL SECTION: THERE IS A CONCERN ABOUT THE
 SUPPORT OF THE SECOND FLOOR TRUSSES. STRUCTURAL LEDGER
 SUPPORTING THE FLOOR TRUSSES IS ANCHORED TO THE WALL
 WITH 5/8" REDHEADS @32" O.C. PROVIDE CALCULATIONS
 SHOWING THAT THE SPECIFIED FASTENER SIZE AND SPACING IS
 ADEQUATE TO SUPPORT THE STRUCTURAL LOAD. SEC. 107.2.1.2
 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS,
 INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE
 STRUCTURAL WALL.
  
 B)ROOF TRUSSES STRUCTURAL SUPPORT SPECIFIED ON THE TWO
 STORY WALL SECTION: DETAIL DOESN'T MATCH TRUSS LAYOUT
 SHOWN ON SECOND FLOOR LOW ROOF FRAMING PLAN ON SHEET
 S-2 FOR ROOF ABOVE MASTER BEDROOM WING. ON THE OTHER
 HAND, IF THIS IS A TYPICAL DETAIL FOR THE ROOF ABOVE
 GARAGE WING, THEN, THERE IS A CONCERN ABOUT THE SUPPORT
 OF THE ROOF TRUSSES. STRUCTURAL LEDGER SUPPORTING THE
 ROOF TRUSSES IS ANCHORED TO THE WALL WITH 1/4" TAPCONS
 @16" O.C. PROVIDE CALCULATIONS SHOWING THAT THE
 SPECIFIED FASTENER SIZE AND SPACING IS ADEQUATE TO
 SUPPORT THE STRUCTURAL LOAD. SEC. 107.2.1.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS,
 INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE
 STRUCTURAL WALL.
  
 C)EAST ELEVATION SPECIFIES "DECORATIVE ALUM. RAILING".
 THIS IS NOT A DECORATIVE RAILING. THIS IS A FUNCTIONAL
 BALCONY GUARDRAIL NOT A DECORATIVE ONE. REVISE AS
 REQUIRED TO AVOID CONFLICTS/DELAYS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5
 FBC-RESIDENTIAL AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: THIS APPLIES TO ALL EXTERIOR ELEVATIONS SHOWING
 THE BALCONY GUARDRAIL.
  
 7- SCHEMATIC HANDRAIL DETAILS ON SHEET A-5:
 A) DETAILS ARE NOT CLEAR. IT LOOKS LIKE THE DETAILS ARE
 APPLICABLE TO COMMERCIAL BUILDINGS NOT FOR SINGLE
 FAMILY RESIDENCE. ALSO, THEY DON'T MATCH HANDRAILS
 SHOWN ON PLANS. REVISE AS REQUIRED. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R311.7.8
 FBC-RESIDENTIAL.
 NOTE: DETAILED STAIR PLAN SPECIFIES "DECORATIVE
 RAILING". THIS IS NOT A DECORATIVE RAILING. THIS IS A
 FUNCTIONAL GUARDRAIL NOT A DECORATIVE ONE. REVISE AS
 REQUIRED TO AVOID CONFLICTS/DELAYS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5
 FBC-RESIDENTIAL AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: DEFERRED SUBMITTAL. SUBMIT HANDRAIL AND GUARDRAIL
 SHOP DRAWINGS REVIEWED BY THE DESIGNER OF RECORD PRIOR
 TO CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
  
 B)REFERENCE CORRECT CODE SECTIONS. SEE CURRENT 2020
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
 SEC. 553 F.S.
  
 8- SHEET S-1: CLARIFY WHY FOOTER F-2 IS SMALLER THAN
 FOOTER F3 IF FOOTER F-3 IS FOR THE ONE STORY SECTION OF
 THE BUILDING AND FOOTING F-2 IS FOR TWO STORY SECTION
 OF THE BUILDING. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 9-SHEET S-2:
 A)SPECIFY CONNECTOR AT BOTH ENDS OF TRUSS GIRDER SHOWN
 ON THE 2ND FLOOR LOW ROOF FRAMING PLAN ABOVE MASTER
 BEDROOM WING, GARAGE WING AND ABOVE COVERED LANAI. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B)SPECIFY UPLIFT TRUSS CONNECTOR FOR TRUSSES RESTING ON
 SECOND FLOOR WALL BY THE GARAGE WING. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C)REVISE ROOF NAILING ZONES SPECIFICATIONS SPECIFIED ON
 SHEET S-2 AND S-3. ROOF SHEATHING NEEDS TO BE NAILED AT
 4 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 D) REVISE STRUCTURAL LEDGER FASTENING SPECIFICATIONS
 SHOWN ON TYPICAL INTERMEDIATE SECTION-1. SEE COMMENT
 #6(A) ABOVE. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- SPECIFY CONNECTOR AT BOTH ENDS OF TRUSS GIRDERS
 SHOWN ON THE UPPER ROOF FRAMING PLAN ON SHEET S-3. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 12- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR: ENTRY DOOR WITH
 TRANSOM ABOVE AS SHOWN ON PLANS, ALL WINDOW TYPES SHOWN
 ON PLANS, ALL DOORS SHOWN ON PLANS, WINDOW MULLIONS
 (AND SPECIFY SIZE), ROOF TILE, ROOF TILE ADHESIVE IF
 USED (SPECIFY SIZE), SHUTTERS IS DOORS/WINDOWS DON'T
 HAVE IMPACT GLASS(AND COMPLETE INSTALLATION SCHEDULE),
 DECORATIVE SHUTTERS SHOWN ON PLANS (AND COMPLETE
 INSTALLATION SCHEDULE), ETC.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL
 AND SPECIFICATIONS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY FINISH FLOORING. SEC. 107.2.1 CITY AMENDMENTS.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN AREAS AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN AREAS AS REQUIRED BY SEC. R302.12
 FBC-RESIDENTIAL.
  
 18- NEED SEPARATE DEMO PERMIT FOR THE DEMOLITION OF
 EXISTING HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,