Plan Review Notes
Plan Review Notes For Permit 21100077
Permit Number 21100077
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-07 16:01:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE FLOOR PLAN INDICATES NEW TILE BUT NO INDICATIONS
 OF WHERE THE NEW TILE IS LOCATED.
  
 FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING
 THE LOCATIONS OF THE BATHROOMS.
  
  
 1A) THERE ARE INDICATIONS OF WORK ON THE BATHROOM WALLS
 THAT ARE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED
 TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 2) THERE ARE INDICATIONS OF NEW TILE BUT NO
 SPECIFICATIONS SHEETS OF TYPE OF TILE OR ANY SOUND
 UNDERLAYMENT THAT INDICATE MEETING THE REQUIREMENTS PER
 NFPA'
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED FROM AROUND THE
 WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND
 NFPA STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS FOR THE
 UNDERLAYMENT AND IF APPLICABLE THE TILE.
  
  
  
 3) THERE APPEARS TO BE CABINETS INDICATED ALONG AN
 OUTSIDE WALL.
  
 THESE CABINETS MAY AFFECT THE FIRE SPRINKLER HEAD
 COVERAGE AND REQUIRE MODIFICATIONS.
  
 A REVIEW OF THE SPRINKLER COVERAGE IS REQQUIRED.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED FIRE
 SPRINKLER CONTRACTORS.
  
 SHOULD THE CONTRACTRO REVIEW AND NO WORK IN REQUIRED, A
 WRITTEN LETTER FROM THE FIRE SPRINKLER COMPANY IS
 REQUIRED TO BE SUBMITTED FOR THE FIRE INSPECTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  