| 2021-10-07 16:01:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE FLOOR PLAN INDICATES NEW TILE BUT NO INDICATIONS |
| | OF WHERE THE NEW TILE IS LOCATED. |
| | |
| | FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING |
| | THE LOCATIONS OF THE BATHROOMS. |
| | |
| | |
| | 1A) THERE ARE INDICATIONS OF WORK ON THE BATHROOM WALLS |
| | THAT ARE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS. |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED |
| | TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF NEW TILE BUT NO |
| | SPECIFICATIONS SHEETS OF TYPE OF TILE OR ANY SOUND |
| | UNDERLAYMENT THAT INDICATE MEETING THE REQUIREMENTS PER |
| | NFPA' |
| | |
| | TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT |
| | CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE |
| | VINYL/LAMINATE ETC AND IS MANUFACTURED FROM AROUND THE |
| | WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC |
| | TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED |
| | FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| | CLASSIFICATION. |
| | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| | FINISHES SHALL |
| | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| | IGNITION |
| | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| | MATERIALS. |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| | THE CLASSES SPECIFIED |
| | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| | CRITICAL RADIANT FLUX |
| | REQUIREMENTS. |
| | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.45 W/CM2, AS DETERMINED |
| | BY THE TEST DESCRIBED IN 10.2.7.3. |
| | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| | INTERIOR FLOOR FINISH |
| | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| | 0.22 W/CM2, BUT LESS |
| | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| | 10.2.7.3. |
| | |
| | PLEASE REVIEW AND PROVIDE SPEC SHEETS FOR THE |
| | UNDERLAYMENT AND IF APPLICABLE THE TILE. |
| | |
| | |
| | |
| | 3) THERE APPEARS TO BE CABINETS INDICATED ALONG AN |
| | OUTSIDE WALL. |
| | |
| | THESE CABINETS MAY AFFECT THE FIRE SPRINKLER HEAD |
| | COVERAGE AND REQUIRE MODIFICATIONS. |
| | |
| | A REVIEW OF THE SPRINKLER COVERAGE IS REQQUIRED. |
| | |
| | ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE |
| | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED FIRE |
| | SPRINKLER CONTRACTORS. |
| | |
| | SHOULD THE CONTRACTRO REVIEW AND NO WORK IN REQUIRED, A |
| | WRITTEN LETTER FROM THE FIRE SPRINKLER COMPANY IS |
| | REQUIRED TO BE SUBMITTED FOR THE FIRE INSPECTION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |