| 2022-03-09 08:21:08 | 03/09/22 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1) DONE. |
| | |
| | 2) DONE. |
| | |
| | 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND |
| | ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC |
| | ACC SEC. 604.8.1.6. |
| | |
| | THE CLEAR FLOOR SPACE FOR THE TURNING RADIUS HAS THE |
| | DOOR SWINGING INTO IT. PLEASE SHOW THAT A 30? X 40? |
| | WILL NOT INTERFERE WITH THE DOOR'S SWING OR HAVE THE |
| | DOOR SWING OUT PER THE 2020 FBC ACC. SEC. 603.2.3DOOR |
| | SWING. |
| | |
| | 4) THE BACKFLOWS FOR THE IRRIGATION AND DOMESTIC WATER |
| | SYSTEMS WILL REQUIRE A SEPARATE PERMIT. THE |
| | MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING |
| | PERMIT SHALL BE SUBMITTED BEFORE INSTALLING THESE |
| | DEVICES. THE DEVICES MUST BE INSTALLED BY A LICENSED |
| | PLUMBING CONTRACTOR.F.S.489.103. |
| | |
| | SHEET C 007 IS NOT AVAILABLE ON THE SET OF PLANS |
| | SUBMITTED. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 5) DONE. |
| | |
| | 6) WHERE IS THE LOCATION OF THE WATER SOURCE? A |
| | BACKFLOW PREVENTION DEVICE WILL BE REQUIRED WHEN |
| | HOOKING TO THE WATER SERVICE. 602.2 POTABLE WATER |
| | REQUIRED. 608.13 BACKFLOW PROTECTION. MEANS OF |
| | PROTECTION AGAINST BACKFLOW SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTIONS 608.13.1 THROUGH 608.13.10. |
| | |
| | THE SHEET IN RESPONSE IS NOT AVAILABLE ON THE SET OF |
| | PLANS SUBMITTED. WOULD YOU PLEASE PROVIDE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 7) DONE. |
| | |
| | 8) DONE. |
| | |
| | 9) DONE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |