| Date |
Text |
| 2021-11-04 07:16:22 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21100054 |
| | 11/4/2021 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| | EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON THE |
| | ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| | FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3. |
| | 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND |
| | ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC |
| | ACC SEC. 604.8.1.6 |
| | 4) THE BACKFLOWS FOR THE IRRIGATION SYSTEM AND THE |
| | DOMESTIC WATER SYSTEM WILL REQUIRE A SEPARATE PERMIT. |
| | MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING |
| | PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF |
| | THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A |
| | LICENSED PLUMBING CONTRACTOR.F.S.489.103. |
| | 5) ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE |
| | (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED |
| | ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN |
| | ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL |
| | NOT BE APPROVED. |
| | 6) WHERE IS THE LOCATION OF THE WATER SOURCE? WHEN |
| | HOOKING TO THE WATER SERVICE A BACKFLOW PREVENTION |
| | DEVICE WILL BE REQUIRED. 602.2 POTABLE WATER REQUIRED. |
| | 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST |
| | BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| | 608.13.1 THROUGH 608.13.10. |
| | 7) THE CURRENT CODE CYCLE IS FLORIDA BUILDING CODE 2020 |
| | 7TH EDITION. PLEASE REMOVE AND UPDATE THE PLANS TO |
| | REFLECT THE CURRENT CODE CYCLE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 8) SEPERATE PERMIT AND PLANS ARE REQUIRED FOR |
| | IRRIGATION WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 9) A SERVICE SINK IS REQUIRED, PLEASE INDICATE WHERE |
| | ONE WILL BE LOCATED ON THE PLANS WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ATELYO BELISLE |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6695 |
| | |