| Plan Review Notes For Permit 21100054 |
| Permit Number |
21100054 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-02 06:16:47 | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC 403.2.1 | | | | | | 2) PLEASE SHOW THAT THE CONDENSATE DRAIN IS TERMINATED | | | TO THE OUTDOORS AND NOT INTO THE BATHROOM LAVITORY. WPB | | | CODE OF ORDINANCES CHAPTER 90 SEC. 90- 126 NUMBER 5. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|