| 2022-08-09 11:33:24 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21100050 |
| | ADD: 2617 DIVISION AVE. |
| | CONT: CHELLY INC. |
| | TEL: 850-900-1349 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 6TH REVIEW |
| | DATE: TUES. AUGUST 09TH/2022 NEW FLOOR PLAN FOR THE 2ND |
| | FLOOR. |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) LIFE SAFETY SHEET VS. A2: |
| | |
| | 2A-F) COMPLIED. |
| | |
| | 2G) SEMI-COMPLIED, 6TH REVIEW. SHEET LS-1 IT APPEARS |
| | THE FIRST-FLOOR PLAN AND 1ST FLOOR STAIR LANDING IS |
| | MISSING, IT APPEARS THE 1ST FLOOR LANDING IS SHOWN ON |
| | THE 2ND FLOOR PLAN AND THE 2ND FLOOR LANDING PLAN IS |
| | SHOWN ON THE 1ST FLOOR PLAN. 107.2.1. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | THE 1ST FLOOR LANDING FOR THE INCLINED CHAIRLIFT AND |
| | DOOR SWING APPEAR TO OVERLAP THE CHAIRLIFT BASE IT |
| | WOULD APPEAR TO BE SOMEWHERE BETWEEN 3-4 INCHES IN |
| | HEIGHT. DISCREPANCY. 107.2.1. CONSTRUCTION DOCUMENTS |
| | SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | THE NEW VERTICAL 2ND FLOOR ADDITION CAN NOT CREATE A |
| | NON-CONFORMITY. 2020 EXISTING BUILDING CODE 1101.2. ALL |
| | NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION |
| | OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL |
| | NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS |
| | BEING MADE REGARDING ACCESSIBILITY, FIRE SAFETY, & |
| | MEANS OF EGRESS SEE 2020 FBC-BUILDING SECTION 1011.3. |
| | THE LIFT DOES NOT INDICATE 80-INCH CLEARANCE FOR A |
| | PERSON THAT MAY NEED A CANE, CROTCHES OR WALKER FOR |
| | ACCESSIBILITY. AS DRAWN THE DETAIL DOES NOT HAVE THE |
| | REQUIRED 80 INCHES REQUIRED BY THE 2020 FBC-BUILDING |
| | CODE SECTION 1011.3. AS DRAWN THE 2ND FLOOR LEVEL ON |
| | THE RIGHT SIDE OF THE PAGE IS IN THE REQUIRED VERTICAL |
| | 80 INCHES FROM THE TOP OF THE INCLINED LIFT TAKEN FROM |
| | THE BACK SIDE OF THE LIFT, NOT THE LEADING EDGE. PLEASE |
| | ALSO REFER TO THE ADVISORY 410.1. 2020 |
| | FBC-ACCESSIBILITY CODE AN ACCESSIBLE ROUTE ALSO |
| | REQUIRES 80 INCHES CLEAR HEIGHT. 2020 FBC-ACCESS. CODE |
| | SECTION 307.4 VERTICAL CLEARANCE SHALL BE 80 INCHES |
| | HIGH MINIMUM. DEFINITIONS: ACCESSIBLE MEANS OF EGRESS. |
| | A CONTINUOUS AND UNOBSTRUCTED WAY OF EGRESS TRAVEL FROM |
| | ANY POINT IN A BUILDING OF FACILITY THAT PROVIDES AN |
| | ACCESSIBLE ROUTE TO AN AREA OF REFUGE, A HORIZONTAL |
| | EXIT OR A PUBLIC WAY. |
| | 5TH REVIEW. SHEET A2 DOES SHOW AN INCLINE LIFT, BUT THE |
| | LIFT DOES NOT INDICATE 80-INCH CLEARANCE FOR A PERSON |
| | THAT MAY NEED A CANE, CROTCHES OR WALKER FOR |
| | ACCESSIBILITY. AS DRAWN THE DETAIL DOES NOT HAVE THE |
| | REQUIRED 80 INCHES REQUIRED BY THE 2020 FBC-BUILDING |
| | CODE SECTION 1011.3. AS DRAWN THE 2ND FLOOR LEVEL ON |
| | THE RIGHT SIDE OF THE PAGE IS IN THE REQUIRED VERTICAL |
| | 80 INCHES FROM THE TOP OF THE INCLINED LIFT TAKEN FROM |
| | THE BACK SIDE OF THE LIFT, NOT THE LEADING EDGE. |
| | THE 2ND ISSUE IS TO DATE THERE HAS BEEN NO CUT SHEETS |
| | ON THE LIFT EITHER THE VERTICAL LIFT OR THE INCLINE |
| | LIFT. PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1. |
| | PLEASE ALSO REFER TO THE ADVISORY 410.1. 2020 |
| | FBC-ACCESSIBILITY CODE. |
| | THE THIRD ISSUE IS WITH NOT HAVING THE CUT SHEETS FOR |
| | THE INCLINE LIFT, THE LIFT AS SHOWN MAY REQUIRE THE |
| | INTERIOR STAIR TO BE WIDER TO ACCOMMODATE THE INCLINE |
| | LIFT. |
| | 4TH REQUEST. SHEETS A-2 & LIFE SAFETY SHEET FOR THE NEW |
| | CONSTRUCTION OF THE 2ND FLOOR TO ACHIEVE VERTICAL |
| | ACCESSIBILITY SHOW THE USE OF AN ADA STAIR LIFT WITHIN |
| | THE STAIRWELL FOR VERTICAL ACCESSIBILITY. PLEASE |
| | PROVIDE THE MANUFACTURERS TECHNICAL SHEETS FOR THE |
| | INCLINED PLATFORM LIFT, HOW IT WILL BE STORED WHEN NOT |
| | IN USE. BECAUSE ACCESSIBLE ROUTE (STAIRS) REQUIRES AN |
| | 80-INCH VERTICAL CLEARANCE. CARE SHOULD BE TAKEN IN |
| | SELECTING LIFTS AS THEY MAY NOT BE EQUALLY SUITABLE FOR |
| | USE BY PEOPLE USING WHEELCHAIRS AND STANDING. IF A LIFT |
| | DOES NOT PROVIDE 80 INCHES VERTICAL CLEARANCE, IT |
| | CANNOT BE CONSIDERED PART OF AN ACCESSIBLE ROUTE IN NEW |
| | CONSTRUCTION. |
| | ONCE A INCLINED LIFT IS SELECTED FOR USE ON STAIRS, |
| | PLEASE PROVIDE A ELEVATION VIEW OF THE STAIRWAY WITH |
| | THE LIFT PARTWAY UP THE STAIRS, SHOWING A STANDING |
| | PERSON AND COMPLYING WITH SECTION 1011.3 HEADROOM |
| | STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF |
| | NOT LESS THAN 80 INCHES MEASURED VERTICALLY FROM A LINE |
| | CONNECTING THE TOP OF THE INCLINED LIFT TO THE STAIR |
| | CEILING. |
| | |
| | 3RD ROUND OF COMMENTS. SHEET A2 MISSING THE VERTICAL |
| | ACCESSIBILITY TO THE FIRST FLOOR AND VERTICAL |
| | ACCESSIBILITY TO THE 2ND FLOOR. |
| | 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT. |
| | NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET |
| | A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT |
| | SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE |
| | SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL |
| | ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE |
| | NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE |
| | YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING |
| | BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT |
| | REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK |
| | MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR |
| | EXISTING BUILDING AN ADDITION THAT AFFECTS THE |
| | ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY |
| | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORID BUILDING CODE, ACCESSIBILITY. |
| | |
| | 3-18) COMPLIED. |
| | |
| | 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED |
| | CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| | OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 20-22) COMPLIED. |
| | |
| | 5TH REVIEW, NEW COMMENTS!! NEW 2ND FLOOR PLAN. |
| | |
| | 23) 2ND REQUEST. THE RESPONSE LETTER STATED A SURVEY |
| | WAS ADDED, I DID NOT SEE ONE ONLY SHEETS SP-1, SP-2 & |
| | C1. |
| | PLEASE PROVIDE A NEW SURVEY TO DETERMINE THE DISTANCE |
| | FROM PROPERTY LINES. 2020 W. P. B. ADMINISTRATIVE |
| | CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | MISSING CODE DATA: |
| | SURVEY |
| | |
| | 24) 2ND REQUEST. THE NEW LOCATION FOR THE 2ND STORY |
| | ADDITION AND EXTERIOR EXIT STAIR PLEASE SHOW ACCESS TO |
| | THE PUBLIC WAY ON THE SITE PLAN. 2020 FBC-BUILDING CODE |
| | 1028.5 & REQUIREMENTS FOR EGRESS COURTS AT PROPERTY |
| | LINES SEE SECTION 1028.4.2. |
| | |
| | 25-35) COMPLIED. |
| | |
| | |
| | |
| | 36) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |