| 2022-05-18 11:00:03 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21100050 |
| | ADD: 2617 DIVISION AVE. |
| | CONT: CHELLY INC. |
| | TEL: 850-900-1349 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 5TH REVIEW |
| | DATE: WED. MAY 18TH/2022 NEW FLOOR PLAN FOR THE 2ND |
| | FLOOR. |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) LIFE SAFETY SHEET VS. A2: |
| | |
| | 2A-F) COMPLIED. |
| | |
| | 2G) SEMI-COMPLIED, 5TH REVIEW. SHEET A5 DOES SHOW A |
| | INCLINE LIFT, BUT THE LIFT DOES NOT INDICATE 80 INCH |
| | CLEARANCE FOR A PERSON THAT MAY NEED A CANE OR WALKER |
| | FOR ACCESSIBILITY. AS DRAWN THE DETAIL DOES NOT HAVE |
| | THE REQUIRED 80 INCHES REQUIRED BY THE 2020 |
| | FBC-BUILDING CODE SECTION 1011.3. AS DRAWN THE 2ND |
| | FLOOR LEVEL ON THE RIGHT SIDE OF THE PAGE IS IN THE |
| | REQUIRED VERTICAL 80 INCHES FROM THE TOP OF THE |
| | INCLINED LIFT TAKEN FROM THE BACK SIDE OF THE LIFT, NOT |
| | THE LEADING EDGE. |
| | THE 2ND ISSUE IS TO DATE THERE HAS BEEN NO CUT SHEETS |
| | ON THE LIFT EITHER THE VERTICAL LIFT OR THE INCLINE |
| | LIFT. PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1. |
| | PLEASE ALSO REFER TO THE ADVISORY410.1. 2020 |
| | FBC-ACCESSIBILITY CODE. |
| | THE THIRD ISSUE IS WITH NOT HAVING THE CUT SHEETS FOR |
| | THE INCLINE LIFT, THE LIFT AS SHOWN MAY REQUIRE THE |
| | INTERIOR STAIR TO BE WIDER TO ACCOMMODATE THE INCLINE |
| | LIFT. |
| | 4TH REQUEST. SHEETS A-2 & LIFE SAFETY SHEET FOR THE NEW |
| | CONSTRUCTION OF THE 2ND FLOOR TO ACHIEVE VERTICAL |
| | ACCESSIBILITY SHOW THE USE OF AN ADA STAIR LIFT WITHIN |
| | THE STAIRWELL FOR VERTICAL ACCESSIBILITY. PLEASE |
| | PROVIDE THE MANUFACTURERS TECHNICAL SHEETS FOR THE |
| | INCLINED PLATFORM LIFT, HOW IT WILL BE STORED WHEN NOT |
| | IN USE. BECAUSE ACCESSIBLE ROUTE (STAIRS) REQUIRES AN |
| | 80-INCH VERTICAL CLEARANCE. CARE SHOULD BE TAKEN IN |
| | SELECTING LIFTS AS THEY MAY NOT BE EQUALLY SUITABLE FOR |
| | USE BY PEOPLE USING WHEELCHAIRS AND STANDING. IF A LIFT |
| | DOES NOT PROVIDE 80 INCHES VERTICAL CLEARANCE, IT |
| | CANNOT BE CONSIDERED PART OF AN ACCESSIBLE ROUTE IN NEW |
| | CONSTRUCTION. |
| | ONCE A INCLINED LIFT IS SELECTED FOR USE ON STAIRS, |
| | PLEASE PROVIDE A ELEVATION VIEW OF THE STAIRWAY WITH |
| | THE LIFT PARTWAY UP THE STAIRS, SHOWING A STANDING |
| | PERSON AND COMPLYING WITH SECTION 1011.3 HEADROOM |
| | STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF |
| | NOT LESS THAN 80 INCHES MEASURED VERTICALLY FROM A LINE |
| | CONNECTING THE TOP OF THE INCLINED LIFT TO THE STAIR |
| | CEILING. |
| | |
| | 3RD ROUND OF COMMENTS. SHEET A2 MISSING THE VERTICAL |
| | ACCESSIBILITY TO THE FIRST FLOOR AND VERTICAL |
| | ACCESSIBILITY TO THE 2ND FLOOR. |
| | 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT. |
| | NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET |
| | A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT |
| | SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE |
| | SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL |
| | ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE |
| | NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE |
| | YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING |
| | BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT |
| | REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK |
| | MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR |
| | EXISTING BUILDING AN ADDITION THAT AFFECTS THE |
| | ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY |
| | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORID BUILDING CODE, ACCESSIBILITY. |
| | |
| | 3-18) COMPLIED. |
| | |
| | 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED |
| | CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| | OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 20-22) COMPLIED. |
| | |
| | NEW COMMENTS!! NEW 2ND FLOOR PLAN. |
| | |
| | 23) PLEASE PROVIDE A NEW SURVEY TO DETERMINE THE |
| | DISTANCE FROM PROPERTY LINES. 2020 W. P. B. |
| | ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | MISSING CODE DATA: |
| | SURVEY |
| | |
| | 24) THE NEW LOCATION FOR THE 2ND STORY ADDITION AND |
| | EXTERIOR EXIT STAIR PLEASE SHOW ACCESS TO THE PUBLIC |
| | WAY ON THE SITE PLAN. 2020 FBC-BUILDING CODE 1028.5. |
| | |
| | 25) PLEASE PROVIDE RISE AND RUN RISER HEIGHT AND TREAD |
| | DEPTH FOR BOTH SETS OF STAIRS IN ACCORDANCE WITH 2020 |
| | FBC-BUILDING 1011.5.2. ALSO PROVIDE COMPLIANCE WITH |
| | 1011.5.5.3 SOLID RISERS FOR BOTH SETS OF STAIRS. |
| | |
| | 26) THE FLOOR PLAN A-2 DOES NOT PORTRAY WHAT HAPPENS |
| | UNDER THE INTERIOR & EXTERIOR STAIRWAY, SHOW COMPLIANCE |
| | WITH 1011.7.4 FIRE RATING. |
| | |
| | 27) PLEASE SHOW HANDRAIL COMPLIANCE WITH 2020 FBC-B |
| | 1011.11. |
| | |
| | 28) THE EXTERIOR STAIR WILL NEED TO SHOE COMPLIANCE FOR |
| | BOTH HANDRAILS IN COMPLIANCE WITH FBC-BUILDING CODE |
| | SECTION 1011.11 AND GUARDS IN COMPLIANCE WITH 1011.3 |
| | AND SECTION1015. |
| | |
| | 29) THE FLOOR PLAN A2 NOR LIFE SAFETY PLAN SHOW THE |
| | LIVE LOADS BOTH STAIRS ARE TO BE BUILT. 2020 |
| | FBC-BUILDING CODE TABLE 1607.1 (30). |
| | |
| | 30) THE FLOOR PLAN A2 DOES NOT INDICATE WHAT TYPE OF |
| | MATERIALS THE STAIRS ARE TO BE BUILT. SHOW COMPLIANCE |
| | WITH SECTION 1011.7 STAIR CONSTRUCTION. BUILDING |
| | CONSTRUCTION TYPE IIB. |
| | |
| | 31) THE COVERSHEET LISTS THE LIVE LOADS FOR THE 2ND |
| | FLOOR FOR CORRIDORS AND OFFICES BUT NOT FOR STORAGE |
| | OCCUPANCIES, SHOW COMPLIANCE WITH THE 2020 FBC-BUILDING |
| | CODE TABLE 1607.1(31). |
| | |
| | 32) OLD COMMENT 2A. WALL TAGS ARE INDICATED ON SHEET |
| | A2. CREATION OR EXTENSION OF NONCONFORMITY. (ADDITIONS) |
| | 2020 FLORIDA EXISTING BUILDING CODE CHAPTER 11 FOR |
| | ADDITIONS AND SECTION 1103.1 FOR VERTICAL ADDITIONS. |
| | UPDATE PLANS. 2020 EXISTING BUILDING CODE SECTION |
| | 1101.2 CREATION OR NONCONFORMITY. AN ADDITION SHALL NOT |
| | CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING |
| | BUILDING TO WHICH THE ADDITION IS BEING MADE WITH |
| | REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE |
| | SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL, |
| | PLUMBING OR ELECTRICAL SYSTEMS. |
| | MISSING INFORMATION IS THE TABLE 501 FIRE RESISTANCE |
| | RATING REQUIREMENTS FOR BUILDING ELEMENTS (HRS). AND |
| | TABLE 602 FIRE-RESISTANCE RATINGS FOR THE EXTERIOR |
| | WALLS BASED ON FIRE SEPARATION DISTANCE OF THE 2020 |
| | FBC-BUILDING CODE AND TABLE 705.8 MAXIMUM AREA OF |
| | EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| | DISTANCE AND DEGREE OF OPENING PROTECTION. ALSO SUPPLY |
| | A CURRENT SURVEY WITH BUILDING DISTANCE TO PROPERTY |
| | LINE. |
| | 1ST ROUND OF COMMENTS. USES FOR EACH AREA ARE UNKNOWN, |
| | EACH AREA DOES NOT HAVE IDENTIFICATION TAGS, THERE ARE |
| | NO WALL TAGS IDENTIFYING WALL TYPES. |
| | |
| | 33) SHEET S-1 SHOW THE USE OF HELICAL PIERS PLEASE |
| | PROVIDE THE SOILS REPORT INDICATING THE INSTALLATION OF |
| | HELICAL PIERS REQUIRED AND LOADS TO BE CARRIED. 2020 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES. |
| | |
| | 34) SHEET S1 ON THE LEFT HAND SIDE OF THE SHEET |
| | INTERIOR END WALL THERE IS SHOWN WHAT APPEARS 3 HELICAL |
| | ANCHORS THE PLAN IS NOT CLEAR IF THIS ARE OF THE PLAN |
| | IS A CONTINUOUS FOOTER OR A ISOLATED PAD FOUNDATION FOR |
| | THE EXISTING COLUMN? 107.2.1. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 35) SHEET S-3 ELEVATIONS SHOWS THE NEW EXTERIOR STAIR |
| | WITH WHAT APPEARS TO BE STEEL POST FOR THE UPPER |
| | LANDING. SHEET S-1 DOES NOT SHOW FOOTERS OR ISOLATED |
| | FOUNDATION PADS TO RECEIVE THE UPRIGHT POST. 107.2.1 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 36) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |