Plan Review Notes
Plan Review Notes For Permit 21100050
Permit Number 21100050
Review Stop B
Sequence Number 5
Notes
Date Text
2022-05-18 11:00:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100050
 ADD: 2617 DIVISION AVE.
 CONT: CHELLY INC.
 TEL: 850-900-1349
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: WED. MAY 18TH/2022 NEW FLOOR PLAN FOR THE 2ND
 FLOOR.
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) LIFE SAFETY SHEET VS. A2:
  
 2A-F) COMPLIED.
  
 2G) SEMI-COMPLIED, 5TH REVIEW. SHEET A5 DOES SHOW A
 INCLINE LIFT, BUT THE LIFT DOES NOT INDICATE 80 INCH
 CLEARANCE FOR A PERSON THAT MAY NEED A CANE OR WALKER
 FOR ACCESSIBILITY. AS DRAWN THE DETAIL DOES NOT HAVE
 THE REQUIRED 80 INCHES REQUIRED BY THE 2020
 FBC-BUILDING CODE SECTION 1011.3. AS DRAWN THE 2ND
 FLOOR LEVEL ON THE RIGHT SIDE OF THE PAGE IS IN THE
 REQUIRED VERTICAL 80 INCHES FROM THE TOP OF THE
 INCLINED LIFT TAKEN FROM THE BACK SIDE OF THE LIFT, NOT
 THE LEADING EDGE.
 THE 2ND ISSUE IS TO DATE THERE HAS BEEN NO CUT SHEETS
 ON THE LIFT EITHER THE VERTICAL LIFT OR THE INCLINE
 LIFT. PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1.
 PLEASE ALSO REFER TO THE ADVISORY410.1. 2020
 FBC-ACCESSIBILITY CODE.
 THE THIRD ISSUE IS WITH NOT HAVING THE CUT SHEETS FOR
 THE INCLINE LIFT, THE LIFT AS SHOWN MAY REQUIRE THE
 INTERIOR STAIR TO BE WIDER TO ACCOMMODATE THE INCLINE
 LIFT.
 4TH REQUEST. SHEETS A-2 & LIFE SAFETY SHEET FOR THE NEW
 CONSTRUCTION OF THE 2ND FLOOR TO ACHIEVE VERTICAL
 ACCESSIBILITY SHOW THE USE OF AN ADA STAIR LIFT WITHIN
 THE STAIRWELL FOR VERTICAL ACCESSIBILITY. PLEASE
 PROVIDE THE MANUFACTURERS TECHNICAL SHEETS FOR THE
 INCLINED PLATFORM LIFT, HOW IT WILL BE STORED WHEN NOT
 IN USE. BECAUSE ACCESSIBLE ROUTE (STAIRS) REQUIRES AN
 80-INCH VERTICAL CLEARANCE. CARE SHOULD BE TAKEN IN
 SELECTING LIFTS AS THEY MAY NOT BE EQUALLY SUITABLE FOR
 USE BY PEOPLE USING WHEELCHAIRS AND STANDING. IF A LIFT
 DOES NOT PROVIDE 80 INCHES VERTICAL CLEARANCE, IT
 CANNOT BE CONSIDERED PART OF AN ACCESSIBLE ROUTE IN NEW
 CONSTRUCTION.
 ONCE A INCLINED LIFT IS SELECTED FOR USE ON STAIRS,
 PLEASE PROVIDE A ELEVATION VIEW OF THE STAIRWAY WITH
 THE LIFT PARTWAY UP THE STAIRS, SHOWING A STANDING
 PERSON AND COMPLYING WITH SECTION 1011.3 HEADROOM
 STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF
 NOT LESS THAN 80 INCHES MEASURED VERTICALLY FROM A LINE
 CONNECTING THE TOP OF THE INCLINED LIFT TO THE STAIR
 CEILING.
  
 3RD ROUND OF COMMENTS. SHEET A2 MISSING THE VERTICAL
 ACCESSIBILITY TO THE FIRST FLOOR AND VERTICAL
 ACCESSIBILITY TO THE 2ND FLOOR.
 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT.
 NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET
 A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT
 SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE
 SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL
 ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE
 NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE
 YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING
 BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT
 REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK
 MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR
 EXISTING BUILDING AN ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORID BUILDING CODE, ACCESSIBILITY.
  
 3-18) COMPLIED.
  
 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 20-22) COMPLIED.
  
 NEW COMMENTS!! NEW 2ND FLOOR PLAN.
  
 23) PLEASE PROVIDE A NEW SURVEY TO DETERMINE THE
 DISTANCE FROM PROPERTY LINES. 2020 W. P. B.
 ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 SURVEY
  
 24) THE NEW LOCATION FOR THE 2ND STORY ADDITION AND
 EXTERIOR EXIT STAIR PLEASE SHOW ACCESS TO THE PUBLIC
 WAY ON THE SITE PLAN. 2020 FBC-BUILDING CODE 1028.5.
  
 25) PLEASE PROVIDE RISE AND RUN RISER HEIGHT AND TREAD
 DEPTH FOR BOTH SETS OF STAIRS IN ACCORDANCE WITH 2020
 FBC-BUILDING 1011.5.2. ALSO PROVIDE COMPLIANCE WITH
 1011.5.5.3 SOLID RISERS FOR BOTH SETS OF STAIRS.
  
 26) THE FLOOR PLAN A-2 DOES NOT PORTRAY WHAT HAPPENS
 UNDER THE INTERIOR & EXTERIOR STAIRWAY, SHOW COMPLIANCE
 WITH 1011.7.4 FIRE RATING.
  
 27) PLEASE SHOW HANDRAIL COMPLIANCE WITH 2020 FBC-B
 1011.11.
  
 28) THE EXTERIOR STAIR WILL NEED TO SHOE COMPLIANCE FOR
 BOTH HANDRAILS IN COMPLIANCE WITH FBC-BUILDING CODE
 SECTION 1011.11 AND GUARDS IN COMPLIANCE WITH 1011.3
 AND SECTION1015.
  
 29) THE FLOOR PLAN A2 NOR LIFE SAFETY PLAN SHOW THE
 LIVE LOADS BOTH STAIRS ARE TO BE BUILT. 2020
 FBC-BUILDING CODE TABLE 1607.1 (30).
  
 30) THE FLOOR PLAN A2 DOES NOT INDICATE WHAT TYPE OF
 MATERIALS THE STAIRS ARE TO BE BUILT. SHOW COMPLIANCE
 WITH SECTION 1011.7 STAIR CONSTRUCTION. BUILDING
 CONSTRUCTION TYPE IIB.
  
 31) THE COVERSHEET LISTS THE LIVE LOADS FOR THE 2ND
 FLOOR FOR CORRIDORS AND OFFICES BUT NOT FOR STORAGE
 OCCUPANCIES, SHOW COMPLIANCE WITH THE 2020 FBC-BUILDING
 CODE TABLE 1607.1(31).
  
 32) OLD COMMENT 2A. WALL TAGS ARE INDICATED ON SHEET
 A2. CREATION OR EXTENSION OF NONCONFORMITY. (ADDITIONS)
 2020 FLORIDA EXISTING BUILDING CODE CHAPTER 11 FOR
 ADDITIONS AND SECTION 1103.1 FOR VERTICAL ADDITIONS.
 UPDATE PLANS. 2020 EXISTING BUILDING CODE SECTION
 1101.2 CREATION OR NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING OR ELECTRICAL SYSTEMS.
 MISSING INFORMATION IS THE TABLE 501 FIRE RESISTANCE
 RATING REQUIREMENTS FOR BUILDING ELEMENTS (HRS). AND
 TABLE 602 FIRE-RESISTANCE RATINGS FOR THE EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE OF THE 2020
 FBC-BUILDING CODE AND TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. ALSO SUPPLY
 A CURRENT SURVEY WITH BUILDING DISTANCE TO PROPERTY
 LINE.
 1ST ROUND OF COMMENTS. USES FOR EACH AREA ARE UNKNOWN,
 EACH AREA DOES NOT HAVE IDENTIFICATION TAGS, THERE ARE
 NO WALL TAGS IDENTIFYING WALL TYPES.
  
 33) SHEET S-1 SHOW THE USE OF HELICAL PIERS PLEASE
 PROVIDE THE SOILS REPORT INDICATING THE INSTALLATION OF
 HELICAL PIERS REQUIRED AND LOADS TO BE CARRIED. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
  
 34) SHEET S1 ON THE LEFT HAND SIDE OF THE SHEET
 INTERIOR END WALL THERE IS SHOWN WHAT APPEARS 3 HELICAL
 ANCHORS THE PLAN IS NOT CLEAR IF THIS ARE OF THE PLAN
 IS A CONTINUOUS FOOTER OR A ISOLATED PAD FOUNDATION FOR
 THE EXISTING COLUMN? 107.2.1. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 35) SHEET S-3 ELEVATIONS SHOWS THE NEW EXTERIOR STAIR
 WITH WHAT APPEARS TO BE STEEL POST FOR THE UPPER
 LANDING. SHEET S-1 DOES NOT SHOW FOOTERS OR ISOLATED
 FOUNDATION PADS TO RECEIVE THE UPRIGHT POST. 107.2.1
 ADDITIONAL INFORMATION IS REQUIRED.
  
 36) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  