| Plan Review Notes For Permit 21100050 |
| Permit Number |
21100050 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-04-06 07:18:59 | 4TH REVIEW FMC | | | PERMIT: 21100050 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M-1, M-2, M-3 HAVE CHANGED, THIS IS NOT THE | | | SAME SHEETS THAT WERE APPROVED. PLEASE PROVIDE A SCOPE | | | OF CHANGES AND WHY THESE SHEETS HA CHANGED. FBC 107.2.1 | | | | | | 2) THE COMMENT RESPONSE SHEET SUBMITTED FOR THE | | | BUILDING REVIEW, COMMENT 18: DESIGNER STATED THAT THE | | | RTU HAS BEEN REMOVED FROM THIS PROJECT. SEE REV. 1 | | | CLOUDED AREA, SHEET P-2. I DO NOT SEE THE CHANGES ON | | | P-2 AND WOULD NOT LOOK THERE AS THIS IS A MECHANICAL | | | CHANGE. PLEASE EXPLAIN THIS CHANGE AND UPDATE THE | | | MECHANICAL DRAWINGS TO REFLECT THIS CHANGE. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|