2022-04-06 07:18:594TH REVIEW FMC
 PERMIT: 21100050
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-1, M-2, M-3 HAVE CHANGED, THIS IS NOT THE
 SAME SHEETS THAT WERE APPROVED. PLEASE PROVIDE A SCOPE
 OF CHANGES AND WHY THESE SHEETS HA CHANGED. FBC 107.2.1
  
 2) THE COMMENT RESPONSE SHEET SUBMITTED FOR THE
 BUILDING REVIEW, COMMENT 18: DESIGNER STATED THAT THE
 RTU HAS BEEN REMOVED FROM THIS PROJECT. SEE REV. 1
 CLOUDED AREA, SHEET P-2. I DO NOT SEE THE CHANGES ON
 P-2 AND WOULD NOT LOOK THERE AS THIS IS A MECHANICAL
 CHANGE. PLEASE EXPLAIN THIS CHANGE AND UPDATE THE
 MECHANICAL DRAWINGS TO REFLECT THIS CHANGE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  