Plan Review Notes For Permit 21100050
Permit Number 21100050
Review Stop B
Sequence Number 4
Notes
Date Text
2022-04-06 08:13:40WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100050
 ADD: 2617 DIVISION AVE.
 CONT: CHELLY INC.
 TEL: 850-900-1349
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: WED. APRIL 06TH/2022
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) LIFE SAFETY SHEET VS. A2:
  
 2A-F) COMPLIED.
  
 2G) SEMI-COMPLIED 4TH REQUEST. SHEETS A-2 & LIFE SAFETY
 SHEET FOR THE NEW CONSTRUCTION OF THE 2ND FLOOR TO
 ACHIEVE VERTICAL ACCESSIBILITY SHOW THE USE OF AN ADA
 STAIR LIFT WITHIN THE STAIRWELL FOR VERTICAL
 ACCESSIBILITY. PLEASE PROVIDE THE MANUFACTURERS
 TECHNICAL SHEETS FOR THE INCLINED PLATFORM LIFT, HOW IT
 WILL BE STORED WHEN NOT IN USE. BECAUSE ACCESSIBLE
 ROUTE (STAIRS) REQUIRES AN 80-INCH VERTICAL CLEARANCE.
 CARE SHOULD BE TAKEN IN SELECTING LIFTS AS THEY MAY NOT
 BE EQUALLY SUITABLE FOR USE BY PEOPLE USING WHEELCHAIRS
 AND STANDING. IF A LIFT DOES NOT PROVIDE 80 INCHES
 VERTICAL CLEARANCE, IT CANNOT BE CONSIDERED PART OF AN
 ACCESSIBLE ROUTE IN NEW CONSTRUCTION.
 ONCE A INCLINED LIFT IS SELECTED FOR USE ON STAIRS,
 PLEASE PROVIDE A ELEVATION VIEW OF THE STAIRWAY WITH
 THE LIFT PARTWAY UP THE STAIRS, SHOWING A STANDING
 PERSON AND COMPLYING WITH SECTION 1011.3 HEADROOM
 STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF
 NOT LESS THAN 80 INCHES MEASURED VERTICALLY FROM A LINE
 CONNECTING THE TOP OF THE INCLINED LIFT TO THE STAIR
 CEILING.
  
 3RD ROUND OF COMMENTS. SHEET A2 MISSING THE VERTICAL
 ACCESSIBILITY TO THE FIRST FLOOR AND VERTICAL
 ACCESSIBILITY TO THE 2ND FLOOR.
 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT.
 NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET
 A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT
 SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE
 SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL
 ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE
 NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE
 YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING
 BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT
 REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK
 MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR
 EXISTING BUILDING AN ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORID BUILDING CODE, ACCESSIBILITY.
  
 3-18) COMPLIED.
  
 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 20-22) COMPLIED.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  