| 2022-04-06 08:13:40 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21100050 |
| | ADD: 2617 DIVISION AVE. |
| | CONT: CHELLY INC. |
| | TEL: 850-900-1349 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: WED. APRIL 06TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) LIFE SAFETY SHEET VS. A2: |
| | |
| | 2A-F) COMPLIED. |
| | |
| | 2G) SEMI-COMPLIED 4TH REQUEST. SHEETS A-2 & LIFE SAFETY |
| | SHEET FOR THE NEW CONSTRUCTION OF THE 2ND FLOOR TO |
| | ACHIEVE VERTICAL ACCESSIBILITY SHOW THE USE OF AN ADA |
| | STAIR LIFT WITHIN THE STAIRWELL FOR VERTICAL |
| | ACCESSIBILITY. PLEASE PROVIDE THE MANUFACTURERS |
| | TECHNICAL SHEETS FOR THE INCLINED PLATFORM LIFT, HOW IT |
| | WILL BE STORED WHEN NOT IN USE. BECAUSE ACCESSIBLE |
| | ROUTE (STAIRS) REQUIRES AN 80-INCH VERTICAL CLEARANCE. |
| | CARE SHOULD BE TAKEN IN SELECTING LIFTS AS THEY MAY NOT |
| | BE EQUALLY SUITABLE FOR USE BY PEOPLE USING WHEELCHAIRS |
| | AND STANDING. IF A LIFT DOES NOT PROVIDE 80 INCHES |
| | VERTICAL CLEARANCE, IT CANNOT BE CONSIDERED PART OF AN |
| | ACCESSIBLE ROUTE IN NEW CONSTRUCTION. |
| | ONCE A INCLINED LIFT IS SELECTED FOR USE ON STAIRS, |
| | PLEASE PROVIDE A ELEVATION VIEW OF THE STAIRWAY WITH |
| | THE LIFT PARTWAY UP THE STAIRS, SHOWING A STANDING |
| | PERSON AND COMPLYING WITH SECTION 1011.3 HEADROOM |
| | STAIRWAYS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF |
| | NOT LESS THAN 80 INCHES MEASURED VERTICALLY FROM A LINE |
| | CONNECTING THE TOP OF THE INCLINED LIFT TO THE STAIR |
| | CEILING. |
| | |
| | 3RD ROUND OF COMMENTS. SHEET A2 MISSING THE VERTICAL |
| | ACCESSIBILITY TO THE FIRST FLOOR AND VERTICAL |
| | ACCESSIBILITY TO THE 2ND FLOOR. |
| | 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT. |
| | NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET |
| | A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT |
| | SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE |
| | SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL |
| | ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE |
| | NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE |
| | YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING |
| | BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT |
| | REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK |
| | MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR |
| | EXISTING BUILDING AN ADDITION THAT AFFECTS THE |
| | ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY |
| | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORID BUILDING CODE, ACCESSIBILITY. |
| | |
| | 3-18) COMPLIED. |
| | |
| | 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED |
| | CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| | OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 20-22) COMPLIED. |
| | |
| | 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |