| 2022-02-08 08:34:03 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21100050 |
| | ADD: 2617 DIVISION AVE. |
| | CONT: CHELLY INC. |
| | TEL: 850-900-1349 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: TUES. FEB. 08TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) LIFE SAFETY SHEET VS. A2: |
| | |
| | 2A-F) COMPLIED. |
| | |
| | 2G)3RD REQUEST. MISSING THE SP SHEET. SHEET A2 MISSING |
| | THE VERTICAL ACCESSIBILITY TO THE FIRST FLOOR AND |
| | VERTICAL ACCESSIBILITY TO THE 2ND FLOOR. |
| | 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT. |
| | NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET |
| | A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT |
| | SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE |
| | SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL |
| | ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE |
| | NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE |
| | YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING |
| | BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT |
| | REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK |
| | MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR |
| | EXISTING BUILDING AN ADDITION THAT AFFECTS THE |
| | ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY |
| | FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORID BUILDING CODE, ACCESSIBILITY. |
| | |
| | 2G)(1) VERTICAL ACCESSIBILITY SEE 201.1.1 BUILDINGS, |
| | STRUCTURES AT A MINIMUM, COMPLY WITH THE REQUIREMENTS |
| | OF THE ADA STANDARDS, FLORIDA ACCESSIBILITY BOARD CAN |
| | ONLY PROVIDE A WAIVER DOWN TO THE ADA STANDARDS. |
| | |
| | 2G(2) 2ND REQUEST. RESPONSE STATES SEE CONTRACTOR |
| | LETTER FOR DISPROPORTIONATE COST. NO LETTER. |
| | 1ST REQUEST. FLORIDA ACCESSIBILITY CODE SECTION: |
| | DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU |
| | ARE TO MEET DISPROPORTIONATE COST. EITHER THE |
| | CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR |
| | LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP |
| | TO THE 20% DISPROPORTIONATE FUNDS($250,000.00 X 0.20%= |
| | $50,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE |
| | BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1 |
| | DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE. |
| | 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO |
| | PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED |
| | AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL |
| | ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE |
| | ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY |
| | BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST |
| | ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN |
| | ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST |
| | ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS |
| | INSTALLING GRAB BARS, ENLARGING TOILET STALLS, |
| | INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET |
| | CONTROLS; (III) COST ASSOCIATED WITH PROVIDING |
| | ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE |
| | TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION |
| | DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV) |
| | COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING |
| | FOUNTAIN. |
| | |
| | 3-18) COMPLIED. |
| | |
| | 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED |
| | CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND |
| | OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 20-22) COMPLIED. |
| | |
| | 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |