Plan Review Notes
Plan Review Notes For Permit 21100050
Permit Number 21100050
Review Stop B
Sequence Number 3
Notes
Date Text
2022-02-08 08:34:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100050
 ADD: 2617 DIVISION AVE.
 CONT: CHELLY INC.
 TEL: 850-900-1349
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. FEB. 08TH/2022
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) LIFE SAFETY SHEET VS. A2:
  
 2A-F) COMPLIED.
  
 2G)3RD REQUEST. MISSING THE SP SHEET. SHEET A2 MISSING
 THE VERTICAL ACCESSIBILITY TO THE FIRST FLOOR AND
 VERTICAL ACCESSIBILITY TO THE 2ND FLOOR.
 2ND REQUEST. THE SP SHEET SHOWS THE LOCATION FOR LIFT.
 NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE SHEET
 A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA LIFT
 SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE
 SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL
 ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE
 NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE
 YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING
 BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT
 REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK
 MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR
 EXISTING BUILDING AN ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORID BUILDING CODE, ACCESSIBILITY.
  
 2G)(1) VERTICAL ACCESSIBILITY SEE 201.1.1 BUILDINGS,
 STRUCTURES AT A MINIMUM, COMPLY WITH THE REQUIREMENTS
 OF THE ADA STANDARDS, FLORIDA ACCESSIBILITY BOARD CAN
 ONLY PROVIDE A WAIVER DOWN TO THE ADA STANDARDS.
  
 2G(2) 2ND REQUEST. RESPONSE STATES SEE CONTRACTOR
 LETTER FOR DISPROPORTIONATE COST. NO LETTER.
 1ST REQUEST. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($250,000.00 X 0.20%=
 $50,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 3-18) COMPLIED.
  
 19) PASSED/ BUILDING PROVISO: WELDED OR BOLTED
 CONNECTIONS. THIS BUILDING CONTAINS EITHER BOLTED AND
 OR WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 20-22) COMPLIED.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  