Plan Review Notes
Plan Review Notes For Permit 21100050
Permit Number 21100050
Review Stop P
Sequence Number 2
Notes
Date Text
2021-12-15 15:49:3812/15/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
 1. ON SHEET A-2
  
 A. MEZZANINE UPSTAIRS DOES NOT SHOW OCCUPANTS WHETHER
 IT APPLIES TO THE 202 FBC SEC 201.1.1 VERTICAL
 ACCESSIBILITY. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
 NEW COMMENT 203.9 DOES NOT EXEMPT, AND THE AMOUNT
 EXEMPTS WHAT WAS SUMMITED HAS MORE THAN FIVE OCCUPANTS
 PER 2020 FBC SEC. 201.1.1. THIS IS NOT CONSIDERED A
 MEZZANINE, AND THE RESTROOM HAS TO BE ACCESSIBLE OR MAY
 BE REQUIRED TO BE UNISEX. WOULD YOU PLEASE TELL US WHAT
 DIRECTION YOU WILL TAKE TO PREVENT DELAY IN YOUR REVIEW
 PROCESS?
  
 B. ON THE RESTROOM TO THE LEFT, IT SHOWS A DOOR OPENING
 TO A HALL FOR THE WATER CLOSET, AND THE DOOR SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO IT PER THE 2020 FBC
 ACC. SEC. 604.8.1.7 WATER CLOSET. IF THERE IS A
 CONFLICT ON THE SECOND OPENING, ONE CAN SWING-OUT.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 H. DONE
  
 I. DONE
  
 2. ON SHEET A-5;
  
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. DONE
  
 E. DONE
  
 F. DONE
  
 G. DONE
  
 H. DONE
  
 I. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER. WOULD YOU PLEASE
 CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS? WOULD YOU PLEASE REMOVE THE SIX
 INCHES MAX?
  
 J. DONE
  
 L. DONE
  
 3. DONE
  
 4. ON SHEET P-1;
 A. DONE
  
 B. DONE
  
 C. DONE
  
 D. WOULD YOU, PLEASE PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATION BASED ON PDI G101 AND THE 2020 AMENDMENT TO
 FBC SEC. 107.3.5.
 NEW COMMENT, GREASE INTERCEPTOR CANNOT BE REMOVED IF IT
 IS A FOOD PROCESSOR. PLEASE PROVIDE FUTURE USE OF THE
 USAGE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. A GREASE
 INTERCEPTOR MAY BE PUT IN LATER WITH REVIEW AND A
 SEPARATE PERMIT BUT MUST BE SHOWN ON THE PLAN.
 WOULD YOU PLEASE VENT THE FLOOR DRAIN IN THE LAST PART
 OF THE BRANCH? A VENT SHALL BE PROVIDED WITH A SYSTEM
 OF VENT PIPING THAT WILL PERMIT THE ADMISSION OR
 EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP
 PER THE 2020 FBC SEC. P 901.2.
  
 E. DONE
  
 5. DONE
  
 6. DONE
  
 7. DONE
  
 8. WOULD YOU PLEASE MOVE THE DIGITAL STAMP ON THE NOTES
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. DONE
  
 10. DONE
  
 11. DONE
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  