2021-12-07 12:17:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100050
 ADD: 2617 DIVISION AVE.
 CONT: CHELLY INC.
 TEL: 850-900-1349
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 07TH/2021
 ACTION: DENIED
  
 1) THE COVER SHEET / CS:
 1A) SEMI- COMPLIED. THE COVERSHEET UNDER THE HEADING OF
 CODE RESEARCH LIST THE WORK TO BE COMPLETED AS,
 RENOVATION AND MEZZANINE ADDITION. PLEASE CORRECT THE
 TERM MEZZANINE TO A 2ND STORY ON THE COVERSHEET AND ALL
 SHEETS STATING MEZZANINE INCLUDING THE TITLE BLOCK. THE
 VERTICAL ADDITION DOES NOT MEET THE REQUIREMENTS OF A
 MEZZANINE FOR AREA LIMITATIONS SECTION 505.2.1 AND
 SECTION 505.2.3 OPENNESS OF THE 2020 FBC-BUILDING CODE.
  
 1B) 2ND REQUEST. THE COVER UNDER THE HEADING OF CODE
 RESEARCH LIST THE CONSTRUCTION TYPE AS IIB-
 NON-SPRINKLERED AND A ALTERATION TYPE AS LEVEL 3.
 PLEASE REVIEW THE 2020 FLORIDA EXISTING BUILDING CODE
 CHAPTER 11 FOR ADDITIONS AND SECTION 1103.1 FOR
 VERTICAL ADDITIONS. UPDATE PLANS INCLUDE 2020 FLORIDA
 EXISTING BUILDING CODE CHAPTER 11 FOR ADDITIONS. 2020
 EXISTING BUILDING CODE SECTION 1101.2 CREATION OR
 NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND
 ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARDS TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING OR ELECTRICAL
 SYSTEMS.
  
 1C) COMPLIED.
  
 1D)2ND REQUEST. SEMI-COMPLIED. THE LS1 SHEET AND A-2
 SHEET SHOW THE NEW 2ND STORY EXTENDED WALLS AS 2 HOUR
 FIRE RATED BUT NOT THE EXISTING WALL THAT IS CLOSE TO
 THE PROPERTY LINE.
 CREATION OR EXTENSION OF NONCONFORMITY. (ADDITIONS)
 2020 FLORIDA EXISTING BUILDING CODE CHAPTER 11 FOR
 ADDITIONS AND SECTION 1103.1 FOR VERTICAL ADDITIONS.
 UPDATE PLANS. 2020 EXISTING BUILDING CODE SECTION
 1101.2 CREATION OR NONCONFORMITY. AN ADDITION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE ADDITION IS BEING MADE WITH
 REGARDS TO ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF MECHANICAL,
 PLUMBING OR ELECTRICAL SYSTEMS.
 MISSING INFORMATION IS THE TABLE 501 FIRE RESISTANCE
 RATING REQUIREMENTS FOR BUILDING ELEMENTS (HRS). AND
 TABLE 602 FIRE-RESISTANCE RATINGS FOR THE EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE OF THE 2020
 FBC-BUILDING CODE AND TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. ALSO SUPPLY
 A CURRENT SURVEY WITH BUILDING DISTANCE TO PROPERTY
 LINE.
  
 1E) NEW COMMENT. THE COVERSHEET UNDER CODE RESEARCH
 DOES NOT LIST THE LIVE FLOOR LOADS FOR THE 2ND FLOOR.
 2020 FBC-TABLE 1607.1 LIVE LOADS.
  
 2) LIFE SAFETY SHEET VS. A2:
  
 2A) SEMI-COMPLIED. WALL TAGS. CREATION OR EXTENSION OF
 NONCONFORMITY. (ADDITIONS) 2020 FLORIDA EXISTING
 BUILDING CODE CHAPTER 11 FOR ADDITIONS AND SECTION
 1103.1 FOR VERTICAL ADDITIONS. UPDATE PLANS. 2020
 EXISTING BUILDING CODE SECTION 1101.2 CREATION OR
 NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND
 ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARDS TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING OR ELECTRICAL
 SYSTEMS.
 MISSING INFORMATION IS THE TABLE 501 FIRE RESISTANCE
 RATING REQUIREMENTS FOR BUILDING ELEMENTS (HRS). AND
 TABLE 602 FIRE-RESISTANCE RATINGS FOR THE EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE OF THE 2020
 FBC-BUILDING CODE AND TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. ALSO SUPPLY
 A CURRENT SURVEY WITH BUILDING DISTANCE TO PROPERTY
 LINE.
 1ST ROUND OF COMMENTS. USES FOR EACH AREA ARE UNKNOWN,
 EACH AREA DOES NOT HAVE IDENTIFICATION TAGS, THERE ARE
 NO WALL TAGS IDENTIFYING WALL TYPES, THEY ARE FOUND ON
 A2 BUT NOT THE LIFE SAFETY SHEET.
  
 2B) COMPLIED.
  
 2C) SEMI-COMPLIED. CREATION OR EXTENSION OF
 NONCONFORMITY. (ADDITIONS) 2020 FLORIDA EXISTING
 BUILDING CODE CHAPTER 11 FOR ADDITIONS AND SECTION
 1103.1 FOR VERTICAL ADDITIONS. UPDATE PLANS. 2020
 EXISTING BUILDING CODE SECTION 1101.2 CREATION OR
 NONCONFORMITY. AN ADDITION SHALL NOT CREATE OR EXTEND
 ANY NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARDS TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING OR ELECTRICAL
 SYSTEMS.
 MISSING INFORMATION IS THE TABLE 501 FIRE RESISTANCE
 RATING REQUIREMENTS FOR BUILDING ELEMENTS (HRS). AND
 TABLE 602 FIRE-RESISTANCE RATINGS FOR THE EXTERIOR
 WALLS BASED ON FIRE SEPARATION DISTANCE OF THE 2020
 FBC-BUILDING CODE AND TABLE 705.8 MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE AND DEGREE OF OPENING PROTECTION. ALSO SUPPLY
 A CURRENT SURVEY WITH BUILDING DISTANCE TO PROPERTY
 LINE.
  
 1ST ROUND OF COMMENTS. LIFE SAFETY SHEET DOES NOT
 INDICATE IF THERE IS ANY FIRE RATED WALLS. SHEET A2
 DOES PROVIDE A WALL LEGEND WITH A DENOTATION FOR
 EXISTING 1 HR. FIRE RATED WALLS. PLEASE NOTE THE NEW
 VERTICAL ADDITION IT APPEARS WILL REQUIRE AN EXTERIOR
 WALL TO BE FIRE RATED, BECAUSE OF THE CLOSENESS TO THE
 PROPERTY LINE. THE SURVEY WILL PROVIDE THE DISTANCE
 FROM THE PROPERTY LINE AND THE PLAN WILL REQUIRE AN
 UPDATE IN ACCORDANCE WITH FIRE RATING WITH TABLE 602 OF
 THE 2020 FBC-BUILDING CODE FOR EITHER THE BUILDING TYPE
 OR OCCUPANCY CLASSIFICATION FOR THE NEW ADDITION.
  
 2D) 2ND REQUEST. THE LIFE SAFETY PLAN EGRESS NOTES NOTE
 2 DECLARES 0-50 PERSONS 1 EXIT REQUIRED, > 50 OCCUPANTS
 2 EXITS REQUIRED. THERE IS NO MENTION OF COMMON PATH OF
 TRAVEL. FOR THE NEW 2ND FLOOR ADDITION THE TRAVEL
 DISTANCE IS SHOWN AT 130 FT., IT WILL BE FURTHER TO BE
 SHOWN PARALLEL TO THE STAIR RISERS AND TO THE NEAREST
 EXIT DOOR. PLEASE REVIEW SPACES WITH ONE EXIT OR EXIT
 ACCESS DOORWAY FOR B OCCUPANCIES NON-SPRINKLERED
 BUILDINGS LIMITED TO 49 OCCUPANTS AND 100 FEET SEE
 TABLE 1006.2.1 AND BECAUSE THIS IS A TRUE 2ND FLOOR
 LOOK AT TABLE 1006.3.2(2) FIRST STORY ABOVE GRADE IT?S
 THE SAME LIMITED TO 49 OCCUPANTS, 100 FEET FOR
 NON-SPRINKLERED BUILDING F OCCUPANCY. THE INTERIOR EXIT
 NEEDS TO BE RATED ON THE 2ND FLOOR AS WELL TO BE A
 VERTICAL EXIT.
  
 2E) SEMI-COMPLIED. THE RESPONSE FOR ENCLOSED STAIRWAY
 INDICATES SEE CLOUDED AREA REV. 1 WALL LEGEND. THE 1ST
 FLOOR SHOWS A 1 HOUR FIRE RATED WALL BUT A GUARDRAIL ON
 THE 2ND STORY, NO 1 HOUR FIRE RATED STAIR ENCLOSURE.
 1ST ROUND COMMENT. THE LIFE SAFETY PLAN AND A-2 WILL
 NEED TO SHOW AN ENCLOSED EXIT IN CONFORMANCE WITH
 INTERNAL EXIT STAIRWAYS SECTION 1023.1, 1023.2 1023.3.
  
 2F) 2ND REQUEST. SHEET A6 DETAIL 8 IS FOR GUARDRAIL
 DETAILS AND THE DETAIL DOES NOT SHOW THE LANDINGS FOR
 1ST FLOOR OR 2ND FLOOR. THE LIFE SAFETY PLAN IS SILENT
 TO THE STAIRWAY, RISER, RUN, LOADING OF THE STAIR AND
 THE MATERIAL THE STAIRS ARE TO BE CONSTRUCTED FROM.
 PLEASE SHOW COMPLIANCE WITH 1011.2 1011.3 1011.5
 1011.5.5.3, 1011.6 & 1011.7 STAIRWAY CONSTRUCTION.
  
 2G)SEMI-COMPLIED. THE SP SHEET SHOWS THE LOCATION FOR
 LIFT. NO DETAILS FOR THE 2ND FLOOR. RESPONSE STATES SEE
 SHEET A-2 FOR LIFT TO 2ND FLOOR. NOT THERE, THE LULA
 LIFT SHOULD ALSO SHOW ON THE LIFE SAFETY PLAN. THE LIFE
 SAFETY PLAN HAS TO ISSUES AT LEAST WITH VERTICAL
 ACCESSIBILITY, THE 1ST IS VERTICAL ACCESSIBILITY TO THE
 NEW 2ND FLOOR, THE 2ND AN ACCESSIBLE ENTRANCE, WHERE
 YOU DO NOT GO UP A RAMP FOR VEHICLES. THE 2020 EXISTING
 BUILDING CODE FOR ADDITIONS SEE SECTION 1105.1 IT
 REFERS YOU BACK TO THE ACCESSIBILITY CODE, NEW WORK
 MUST COMPLY WITH THE ACCESSIBILITY CODE AND FOR
 EXISTING BUILDING AN ADDITION THAT AFFECTS THE
 ACCESSIBILITY TO OR CONTAINS AN AREA OF. PRIMARY
 FUNCTION SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORID BUILDING CODE, ACCESSIBILITY.
  
 2G)(1) VERTICAL ACCESSIBILITY SEE 201.1.1 BUILDINGS,
 STRUCTURES AT A MINIMUM, COMPLY WITH THE REQUIREMENTS
 OF THE ADA STANDARDS, FLORIDA ACCESSIBILITY BOARD CAN
 ONLY PROVIDE A WAIVER DOWN TO THE ADA STANDARDS.
  
 2G(2) FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($250,000.00 X 0.20%=
 $50,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 3) COMPLIED.
  
 4) SHEET A6 DETAILS: DETAILS SHOW RESTROOM INTERIOR
 ELEVATIONS DETAILS 1 & 2 FOR GRAB BARS, NO DIMENSIONS
 ARE SHOWN.
  
 4-7) COMPLIED.
  
 8-17)
  
  
 18) SHEET S-2 THE ROOF FRAMING PLAN DOES NOT INDICATE
 ANY EXTRA ROOF FRAMING FOR THE ROOF TOP MECHANICAL
 UNIT, OR SHEET M2, SHEET P-2 SHOWS THE RTU ON THE ROOF.
 PLEASE PROVIDE DETAILS FOR BAR JOIST POINT LOADING,
 INFILL STEEL FOR FRAME AND WELDING DETAILS.
  
 19) SHEET S2 THE 2ND FLOOR FRAMING SHOWS STEEL
 CONNECTIONS FOR COLUMNS AND STEEL BEAMS.
 BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THIS
 BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 20-22) COMPLIED.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  