| 2021-10-25 14:02:01 | 10/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET A-2 |
| | A. MEZZANINE UPSTAIRS DOES NOT SHOW OCCUPANTS TO |
| | DETERMINE IF IT APPLIES TO THE 202 FBC SEC 201.1.1 |
| | VERTICAL ACCESSIBILITY. WOULD YOU PLEASE CLARIFY PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. ON THE RESTROOM TO THE LEFT, IT SHOWS A DOOR OPENING |
| | TO A HALL FOR THE WATER CLOSET, AND THE DOOR SHALL BE |
| | LOCATED IN THE CORNER, DIAGONAL TO IT PER THE 2020 FBC |
| | ACC. SEC. 604.8.1.7 WATER CLOSET. IF THERE IS A |
| | CONFLICT ON THE OPENING OF THE SECOND, THEN ONE CAN |
| | SWING-OUT. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN THE SHOWER, THE DOOR TO THE INSIDE, WOULD YOU |
| | PLEASE SHOW THE 5-FOOT TURNING RADIUS WITH DIMENSION |
| | AND THE CLEAR FLOOR SPACE AGAINST IT PER THE 2020 FBC |
| | ACC. SEC. 304.3. |
| | |
| | D. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A |
| | PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX |
| | PER THE 2020 FBC SECTION P 403.2. |
| | |
| | E. WOULD YOU PLEASE PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS? PROVIDE A SCHEDULE ON THE PLAN SHOWING |
| | THE REQUIRED AND PROVIDE THE NUMBER OF FIXTURES PER |
| | TABLE 403.3 FBC P. PLEASE NOTE THAT SERVICE SINKS ARE |
| | REQUIRED FOR F OCCUPANCY. AN EMERGENCY SHOWER AND |
| | EYEWASH STATION MAY BE REQUIRED FOR THE F OCCUPANCY |
| | DEPENDING UPON THE DEPARTMENT OF HEALTH, DEPARTMENT OF |
| | AGRICULTURE, OSHA, OR OTHER GOVERNING AGENCY |
| | REQUIREMENTS. WOULD YOU PLEASE CONTACT THOSE AGENCIES |
| | FOR FURTHER INFORMATION. |
| | |
| | F. THERE IS A DRINKING FOUNTAIN ON OTHER DRAWINGS, AND |
| | THESE ONE AND OTHERS ARE MISSING THE DRINKING FOUNTAIN. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | H. WOULD YOU PLEASE SHOW THE 30 X 48 IN. CLEAR FLOOR |
| | SPACE FOR A FORWARD APPROACH TO THE |
| | WHEELCHAIR-ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC |
| | SEC. 602.2. |
| | |
| | I. WOULD YOU PLEASE SHOW A SERVICE SINK (MOP SINK), AND |
| | THE SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN |
| | ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 AND |
| | 2020 FBC SEC. P 310.3. WOULD YOU PLEASE MAKE A NOTE ON |
| | THIS SHEET? |
| | |
| | 2. ON SHEET A-5; |
| | A. THE DETAIL FOR 10 AND 11 HAVE NUMBERS AND NO |
| | SCHEDULE TO REFER TO. WOULD YOU PLEASE PROVIDE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. DETAIL 10 GRAB BARS SHALL BE MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | C. ON DETAIL 7 AND 8, WOULD YOU PLEASE SHOW THE PIPE |
| | SIZE ON THE FIRESTOP SYSTEM SUBMITTED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DETAIL 11, THE REFLECTIVE PART OF THE MIRROR |
| | NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER THE |
| | 2020 FBC ACC SEC. 603.3. |
| | |
| | E. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SINK |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | F. ON DETAIL 10, THE TOILET PAPER DISPENSERS SHALL BE 7 |
| | INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE |
| | WATER CLOSET MEASURED TO THE CENTERLINE OF DISPENSER |
| | PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | G. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES |
| | MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020 |
| | FBC ACC SEC. 604.4 SEATS. |
| | |
| | H. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER |
| | 2020 FBC P 425.3 WATER CLOSET SEATS. |
| | |
| | I. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL, |
| | WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16 |
| | INCHES TO 18 INCHES TO THE CENTER. WOULD YOU PLEASE |
| | CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | J. THE HORIZONTAL GRAB BARS ON THE REAR NEED TO BE |
| | MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES |
| | TO THE WALL AND 24 INCHES TO THE OPEN SIDE PER THE |
| | 604.5.2 REAR WALL. |
| | |
| | L. ON DETAIL 11, THE WATER CLOSET, THE ACTUAL NUMBER |
| | FOR THE TOILET FROM THE WALL IS 16 INCHES TO 18 INCHES |
| | TO THE CENTER. WOULD YOU PLEASE CORRECT PER THE 2020 |
| | FBC ACC SEC. 604.2 LOCATION. |
| | |
| | 3. ON SHEET A-7, DETAIL 7 SHOWS SINK IN IT, BUT IT IS |
| | THE HEIGHT AT 34 INCHES. WOULD YOU PLEASE CORRECT PER |
| | THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS? |
| | |
| | 4. ON SHEET P-1; |
| | A. THE FLOOR DRAIN IS NOT LABELED OR SIZED, AND FLOOR |
| | SINKS ARE NOT LABELED. |
| | |
| | B. WOULD YOU PLEASE SHOE ALL TRAP PRIMER FOR THE |
| | MISSING FLOOR DRAIN PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. WOULD YOU PLEASE PROVIDE A DETAIL OF THE |
| | THREE-COMPARTMENT WITH ITS REFERENCE TO ITS PAGE PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. WOULD YOU PLEASE PROVIDE GREASE INTERCEPTOR SIZING |
| | CALCULATION BASED ON PDI G101 AND THE 2020 AMENDMENT TO |
| | FBC SEC. 107.3.5 |
| | |
| | E. THE KITCHEN HAS NO DRAIN FOR THE KITCHEN SINK. WOULD |
| | YOU PLEASE CORRECT AND SHOW ON ISOMETRIC FOR P-3 AS |
| | WELL PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 5. ON SHEET P-2, IT SHOWS THE RAIN LEADER, SO WOULD YOU |
| | PLEASE PROVIDE THE STROM SIZING TABLE USED AND SHOW ON |
| | THE ISOMETRIC DRAWING ON SHEET P3 PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 6. ON SHEET, P-3, WOULD YOU PLEASE SHOW THE WATER |
| | SERVICE VALVE, HAMMER ARRESTOR FOR DF, THE SHUT-OFF |
| | VALVES FOR RESTROOM GROUPS, AND HOSE BIBBS VALVES AS |
| | NOTED ON P-4 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. ON SHEET P-4, TEMPERED WATER SHALL BE DELIVERED FROM |
| | LAVATORIES AND GROUP WASH FIXTURES IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020 FBC |
| | SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | |
| | 8. WOULD YOU PLEASE MOVE THE DIGITAL STAMP ON THE NOTES |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 9. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. |
| | |
| | 10. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF |
| | THE WATER CLOSET PER THE 2020 ACC SEC. 604.6 FLUSH |
| | CONTROLS. |
| | |
| | 11. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE BREAKROOM SINK PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |