Date Text
2021-10-25 14:02:0110/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-2
 A. MEZZANINE UPSTAIRS DOES NOT SHOW OCCUPANTS TO
 DETERMINE IF IT APPLIES TO THE 202 FBC SEC 201.1.1
 VERTICAL ACCESSIBILITY. WOULD YOU PLEASE CLARIFY PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 B. ON THE RESTROOM TO THE LEFT, IT SHOWS A DOOR OPENING
 TO A HALL FOR THE WATER CLOSET, AND THE DOOR SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO IT PER THE 2020 FBC
 ACC. SEC. 604.8.1.7 WATER CLOSET. IF THERE IS A
 CONFLICT ON THE OPENING OF THE SECOND, THEN ONE CAN
 SWING-OUT. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN THE SHOWER, THE DOOR TO THE INSIDE, WOULD YOU
 PLEASE SHOW THE 5-FOOT TURNING RADIUS WITH DIMENSION
 AND THE CLEAR FLOOR SPACE AGAINST IT PER THE 2020 FBC
 ACC. SEC. 304.3.
  
 D. WOULD YOU PLEASE LABEL THE RESTROOM THAT REQUIRED A
 PUBLIC FACILITY TO PROVIDE SIGNS THAT DESIGNATE THE SEX
 PER THE 2020 FBC SECTION P 403.2.
  
 E. WOULD YOU PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS? PROVIDE A SCHEDULE ON THE PLAN SHOWING
 THE REQUIRED AND PROVIDE THE NUMBER OF FIXTURES PER
 TABLE 403.3 FBC P. PLEASE NOTE THAT SERVICE SINKS ARE
 REQUIRED FOR F OCCUPANCY. AN EMERGENCY SHOWER AND
 EYEWASH STATION MAY BE REQUIRED FOR THE F OCCUPANCY
 DEPENDING UPON THE DEPARTMENT OF HEALTH, DEPARTMENT OF
 AGRICULTURE, OSHA, OR OTHER GOVERNING AGENCY
 REQUIREMENTS. WOULD YOU PLEASE CONTACT THOSE AGENCIES
 FOR FURTHER INFORMATION.
  
 F. THERE IS A DRINKING FOUNTAIN ON OTHER DRAWINGS, AND
 THESE ONE AND OTHERS ARE MISSING THE DRINKING FOUNTAIN.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 H. WOULD YOU PLEASE SHOW THE 30 X 48 IN. CLEAR FLOOR
 SPACE FOR A FORWARD APPROACH TO THE
 WHEELCHAIR-ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC
 SEC. 602.2.
  
 I. WOULD YOU PLEASE SHOW A SERVICE SINK (MOP SINK), AND
 THE SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE IN
 ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 AND
 2020 FBC SEC. P 310.3. WOULD YOU PLEASE MAKE A NOTE ON
 THIS SHEET?
  
 2. ON SHEET A-5;
 A. THE DETAIL FOR 10 AND 11 HAVE NUMBERS AND NO
 SCHEDULE TO REFER TO. WOULD YOU PLEASE PROVIDE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. DETAIL 10 GRAB BARS SHALL BE MEASURED TO THE TOP OF
 THE GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 C. ON DETAIL 7 AND 8, WOULD YOU PLEASE SHOW THE PIPE
 SIZE ON THE FIRESTOP SYSTEM SUBMITTED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL 11, THE REFLECTIVE PART OF THE MIRROR
 NEEDS TO BE 40 INCHES TO THE REFLECTIVE SIDE PER THE
 2020 FBC ACC SEC. 603.3.
  
 E. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SINK
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 F. ON DETAIL 10, THE TOILET PAPER DISPENSERS SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF DISPENSER
 PER THE 2020 FBC ACC SEC. 604.7.
  
 G. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 H. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 I. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER. WOULD YOU PLEASE
 CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 J. THE HORIZONTAL GRAB BARS ON THE REAR NEED TO BE
 MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES
 TO THE WALL AND 24 INCHES TO THE OPEN SIDE PER THE
 604.5.2 REAR WALL.
  
 L. ON DETAIL 11, THE WATER CLOSET, THE ACTUAL NUMBER
 FOR THE TOILET FROM THE WALL IS 16 INCHES TO 18 INCHES
 TO THE CENTER. WOULD YOU PLEASE CORRECT PER THE 2020
 FBC ACC SEC. 604.2 LOCATION.
  
 3. ON SHEET A-7, DETAIL 7 SHOWS SINK IN IT, BUT IT IS
 THE HEIGHT AT 34 INCHES. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET P-1;
 A. THE FLOOR DRAIN IS NOT LABELED OR SIZED, AND FLOOR
 SINKS ARE NOT LABELED.
  
 B. WOULD YOU PLEASE SHOE ALL TRAP PRIMER FOR THE
 MISSING FLOOR DRAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. WOULD YOU PLEASE PROVIDE A DETAIL OF THE
 THREE-COMPARTMENT WITH ITS REFERENCE TO ITS PAGE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATION BASED ON PDI G101 AND THE 2020 AMENDMENT TO
 FBC SEC. 107.3.5
  
 E. THE KITCHEN HAS NO DRAIN FOR THE KITCHEN SINK. WOULD
 YOU PLEASE CORRECT AND SHOW ON ISOMETRIC FOR P-3 AS
 WELL PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 5. ON SHEET P-2, IT SHOWS THE RAIN LEADER, SO WOULD YOU
 PLEASE PROVIDE THE STROM SIZING TABLE USED AND SHOW ON
 THE ISOMETRIC DRAWING ON SHEET P3 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET, P-3, WOULD YOU PLEASE SHOW THE WATER
 SERVICE VALVE, HAMMER ARRESTOR FOR DF, THE SHUT-OFF
 VALVES FOR RESTROOM GROUPS, AND HOSE BIBBS VALVES AS
 NOTED ON P-4 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET P-4, TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2020 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 8. WOULD YOU PLEASE MOVE THE DIGITAL STAMP ON THE NOTES
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 10. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF
 THE WATER CLOSET PER THE 2020 ACC SEC. 604.6 FLUSH
 CONTROLS.
  
 11. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE BREAKROOM SINK PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  