| 2021-10-15 09:56:19 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21100050 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE HEAT LOAD CALCULATIONS FOR THE |
| | CORRECT CITY ( WEST PALM BEACH). FBC 107.2.1 |
| | |
| | 2) SHEET M2: PLEASE SUBMIT A DRAWING THAT SHOWS THE |
| | WORDING FOR THE MEZZANINE BATH EXHAUST FAN. THE WORDS |
| | ARE CUT OFF AND ARE NOT READABLE ON THIS DRAWING. FBC |
| | 107.2.1 |
| | |
| | 3) PLEASE PROVIDE THE USE OF THIS BUILDING. FBC 107.2.1 |
| | |
| | 4) PLEASE PROVIDE THE SPECIFICATIONS FOR THE RTU?S AND |
| | ALL EQUIPMENT FOR THIS PROJECT. FBC 107.2.1 |
| | |
| | 5) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE FOR THIS BUILDING. FBC M 403.3.1.1 & TABLE |
| | 403.3.1.1 |
| | |
| | 6) SHEET M-3 INDICATES THE MECHANICAL SYSTEMS ARE SPLIT |
| | SYSTEMS WITH THE AHU BEING HUNG FROM THE STRUCTURE AND |
| | THE C.U. BEING MOUNTED ON THE ROOF. THE OUTDOOR AIR |
| | CALCULATION INDICATES THAT THE MECHANICAL SYSTEMS ARE |
| | RTU?S BUT ONLY SHOWS 3 RTU?S. PLEASE PROVIDE CONSISTENT |
| | INFORMATION ON THE MECHANICAL DRAWINGS. FBC 107.2.1 |
| | |
| | 7) SHEET M-3 HAS A NOTE TO GO TO A/C FLOOR PLAN FOR |
| | CONDENSATE TERMINATION, PLEASE SHOW THE CONDENSATE |
| | PIPING AND TERMINATION LOCATION ON THE DRAWINGS. FBC M |
| | 307. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |