Plan Review Notes
Plan Review Notes For Permit 21100050
Permit Number 21100050
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-07 11:45:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATION OF COMMON PATH OF TRAVEL
 DISTANCE FROM THE MEZZANINE OF 71'6"
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE,
 STORY, OR PORTION THEREOF SHALL BE NOT LESS THAN TWO,
 EXCEPT UNDER ONE OF
 THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN
 CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR
 BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS OF
 CHAPTERS
 11 THROUGH 43 ARE MET.
  
 7.5.1.1.4 WHERE COMMON PATHS OF TRAVEL ARE PERMITTED
 FOR AN OCCUPANCY
 IN CHAPTERS 11 THROUGH 43, SUCH COMMON PATHS OF TRAVEL
 SHALL BE PERMITTED
 BUT SHALL NOT EXCEED THE LIMIT SPECIFIED.
  
 PER NFPA 101, CH 40
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS.
  
 40.2.5.1 GENERAL. MEANS OF EGRESS, ARRANGED IN
 ACCORDANCE WITH SECTION
 7.5, SHALL NOT EXCEED THAT PROVIDED BY TABLE 40.2.5.1.
  
 THE MAX DISTANCE OF A UNSPRINKLERED OCCUPANCY IS 50'
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) THE LS SHEET INDICATES AN OCCUPANCY LOAD OF 75 AND
 DOOR # 4 SWINGING AGAINST THE DIRECTION OF EGRESS.
  
 PER NFPA 101 CH 7
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPANCIES,
 AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  