2021-11-02 13:49:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100050
 ADD: 2617 DIVISION AVE.
 CONT: CHELLY INC.
 TEL: 850-900-1349
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 02/2021
 ACTION: DENIED
  
 1) THE COVER SHEET / CS:
 1A) THE COVER UNDER THE HEADING OF CODE RESEARCH LIST
 THE WORK TO BE COMPLETED AS, RENOVATION AND MEZZANINE
 ADDITION. PLEASE CORRECT THE TERM MEZZANINE TO A 2ND
 STORY. THE VERTICAL ADDITION DOES NOT MEET THE
 REQUIREMENTS OF A MEZZANINE FOR AREA LIMITATIONS
 SECTION 505.2.1 AND SECTION 505.2.3 OPENNESS OF THE
 2020 FBC-BUILDING CODE.
  
 1B) THE COVER UNDER THE HEADING OF CODE RESEARCH LIST
 THE CONSTRUCTION TYPE AS IIB- NON-SPRINKLERED AND A
 ALTERATION TYPE AS LEVEL 3. PLEASE REVIEW THE 2020
 EXISTING BUILDING CODE CHAPTER 11 FOR ADDITIONS AND
 SECTION 1103.1 FOR VERTICAL ADDITIONS. UPDATE PLANS.
  
 1C) OCCUPANCY CLASSIFICATION & OCCUPANT LOAD. PLEASE
 PROVIDE THE SQUARE FOOT AREA FOR EACH TYPE OF OCCUPANCY
 AND THE OCCUPANT LOAD FACTOR USED IN THE TABLE 1004.5.
 PLEASE PROVIDE THE OCCUPANCY TYPE, OCCUPANCY LOAD AND
 SQUARE FOOTAGE BROKE DOWN FOR EACH SEGMENT OF THE
 BUILDING AND TOTAL SQ. FOOTAGE AND OCCUPANT LOAD.
 PLEASE NOTE THE LIFE SAFETY SHEET GIVE A TOTAL OCCUPANT
 LOAD FOR EACH OCCUPANCY BUT NOT PER SPACE.
  
 1D) MISSING INFORMATION IS THE TABLE 501 FIRE
 RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
 (HRS). AND TABLE 602 FIRE-RESISTANCE RATINGS FOR THE
 EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE OF THE
 2020
 FBC-BUILDING CODE. ALSO SUPPLY A CURRENT SURVEY WITH
 BUILDING DISTANCE TO PROPERTY LINE.
  
 2) LIFE SAFETY SHEET VS. A2:
  
 2A) USES FOR EACH AREA ARE UNKNOWN, EACH AREA DOES NOT
 HAVE IDENTIFICATION TAGS, THERE ARE NO WALL TAGS
 IDENTIFYING WALL TYPES, THEY ARE FOUND ON A2 BUT NOT
 THE LIFE SAFETY SHEET.
  
 2B) SHEET A2 AND LIFE SAFETY SHEETS BOTH LIST THE OVER
 ALL OCCUPANT LOADS PER OCCUPANCY TYPE, BUT THE OCCUPANT
 LOAD FOR BUSINESS IS SHOWN AS 20 OCCUPANTS @ 1,958 SQ.
 FT. PLEASE BE AWARE THE OCCUPANT LOAD FACTOR WAS
 CHANGED FROM 100 TO 150 FOR THE BUSINESS OCCUPANCY IN
 THE 2020 FBC-B. 1958 S. F./ 150 = 13.05 OR 14
 OCCUPANTS.
  
 2C) LIFE SAFETY SHEET DOES NOT INDICATE IF THERE IS ANY
 FIRE RATED WALLS. SHEET A2 DOES PROVIDE A WALL LEGEND
 WITH A DENOTATION FOR EXISTING 1 HR. FIRE RATED WALLS.
 PLEASE NOTE THE NEW VERTICAL ADDITION IT APPEARS WILL
 REQUIRE AN EXTERIOR WALL TO BE FIRE RATED, BECAUSE OF
 THE CLOSENESS TO THE PROPERTY LINE. THE SURVEY WILL
 PROVIDE THE DISTANCE FROM THE PROPERTY LINE AND THE
 PLAN WILL REQUIRE AN UPDATE IN ACCORDANCE WITH FIRE
 RATING WITH TABLE 602 OF THE 2020 FBC-BUILDING CODE FOR
 EITHER THE BUILDING TYPE OR OCCUPANCY CLASSIFICATION
 FOR THE NEW ADDITION.
  
 2D) THE LIFE SAFETY PLAN EGRESS NOTES NOTE 2 DECLARES
 0-50 PERSONS 1 EXIT REQUIRED, > 50 OCCUPANTS 2 EXITS
 REQUIRED. THERE IS NO MENTION OF COMMON PATH OF TRAVEL.
 FOR THE NEW 2ND FLOOR ADDITION THE COMMON PATH OF
 TRAVEL IS SHOWN AT 130 FT., IT WILL BE FURTHER TO BE
 SHOWN PARALLEL TO THE STAIR RISERS AND TO THE NEAREST
 EXIT DOOR. PLEASE REVIEW SPACES WITH ONE EXIT OR EXIT
 ACCESS DOORWAY FOR F OCCUPANCIES NON-SPRINKLERED
 BUILDINGS LIMITED TO 49 OCCUPANTS AND 75 FEET SEE TABLE
 1006.2.1 AND BECAUSE THIS IS A TRUE 2ND FLOOR LOOK AT
 TABLE 1006.3.2(2) FIRST STORY ABOVE GRADE IT?S THE SAME
 LIMITED TO 49 OCCUPANTS, 75 FEET FOR NON-SPRINKLERED
 BUILDING F OCCUPANCY.
  
 2E) THE LIFE SAFETY PLAN AND A-2 WILL NEED TO SHOW AN
 ENCLOSED EXIT IN CONFORMANCE WITH INTERNAL EXIT
 STAIRWAYS SECTION 1023.1, 1023.2 1023.3.
  
 2F) THE LIFE SAFETY PLAN IS SILENT TO THE STAIRWAY,
 RISER, RUN, LOADING OF THE STAIR AND THE MATERIAL THE
 STAIRS ARE TO BE CONSTRUCTED FROM. PLEASE SHOW
 COMPLIANCE WITH 1011.2 1011.3 1011.5 1011.5.5.3, 1011.6
 & 1011.7 STAIRWAY CONSTRUCTION.
  
 2G) THE LIFE SAFETY PLAN HAS TO ISSUES AT LEAST WITH
 VERTICAL ACCESSIBILITY, THE 1ST IS VERTICAL
 ACCESSIBILITY TO THE NEW 2ND FLOOR, THE 2ND AN
 ACCESSIBLE ENTRANCE, WHERE YOU DO NOT GO UP A RAMP FOR
 VEHICLES. THE 2020 EXISTING BUILDING CODE FOR ADDITIONS
 SEE SECTION 1105.1 IT REFERS YOU BACK TO THE
 ACCESSIBILITY CODE, NEW WORK MUST COMPLY WITH THE
 ACCESSIBILITY CODE AND FOR EXISTING BUILDING AN
 ADDITION THAT AFFECTS THE ACCESSIBILITY TO OR CONTAINS
 AN AREA OF. PRIMARY FUNCTION SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORID BUILDING CODE,
 ACCESSIBILITY.
  
 2G)(1) VERTICAL ACCESSIBILITY SEE 201.1.1 BUILDINGS,
 STRUCTURES AT A MINIMUM, COMPLY WITH THE REQUIREMENTS
 OF THE ADA STANDARDS, FLORIDA ACCESSIBILITY BOARD CAN
 ONLY PROVIDE A WAIVER DOWN TO THE ADA STANDARDS.
  
 2G(2) FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS($250,000.00 X 0.20%=
 $50,000.00) LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE
 BEING SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 3) DISCREPANCY IN PLANS, THE SHEET S-3 SHOWS WINDOWS IN
 THE NEW ELEVATION FACING DIVISION AVE. WHERE AS SHEET
 A-4 DOES NOT SHOW WINDOWS IN THE SAME ELEVATION VIEW.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY IN THE PLANS.
  
 4) SHEET A6 DETAILS: DETAILS SHOW RESTROOM INTERIOR
 ELEVATIONS DETAILS 1 & 2 FOR GRAB BARS, NO DIMENSIONS
 ARE SHOWN.
  
 4A) GRAB BARS/ RESTROOMS> 2020 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 4B) 2020 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE
 SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 4C) 2017 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR
 WALL. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915
 MM) LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 5) SHEET A2 SHOWS A BREAK ROOM WITH BOTTOM CABINETS AND
 SINK. NO APPROACH IS SHOWN, ACCESS. CODE 606.2 CLEAR
 FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED, SEE
 EXCEPTIONS ALSO, BUT SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE FLOOR PLAN.
  
 6) SHEET A6 DETAIL 4 SHOWS CABINETRY 3 FEET TO THE
 COUNTER HEIGHT. ) 902.1. WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. EXAMPLES
 OF WORK SURFACES INCLUDE WRITING SURFACES, STUDY
 CARRELS, STUDENT LABORATORY STATIONS, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS.
  
 6)(A) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6)(B) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 7) SHEET A5 THE FINISH SCHEDULE INDICATES PAINTED
 SURFACES GYPSUM BOARD. 2020 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS,
 RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 7A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 7B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 7C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 8) SHEET S3 ELEVATIONS SHOW WINDOWS IN THE NEW VERTICAL
 ADDITION. COMPONENTS & CLADDING. PLEASE SUBMIT THE
 COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 9) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 10) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 12) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 13) 2020 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL.
  
 14) 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 15) LATERAL FORCE-RESISTING SYSTEM.FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 16) 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 17) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 18) SHEET S-2 THE ROOF FRAMING PLAN DOES NOT INDICATE
 ANY EXTRA ROOF FRAMING FOR THE ROOF TOP MECHANICAL
 UNIT, OR SHEET M2, SHEET P-2 SHOWS THE RTU ON THE ROOF.
 PLEASE PROVIDE DETAILS FOR BAR JOIST POINT LOADING,
 INFILL STEEL FOR FRAME AND WELDING DETAILS.
  
 19) SHEET S2 THE 2ND FLOOR FRAMING SHOWS STEEL
 CONNECTIONS FOR COLUMNS AND STEEL BEAMS.
 WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 20) THERE IS NO CUT SECTION THROUGH THE 2ND FLOOR
 ADDITION SHOWING IF THERE IS TO BE A PARAPET OR NOT
 PLEASE PROVIDE ADDITIONAL INFORMATION? 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 21) PLEASE BE AWARE OF THE WINDOW NOA SUBMITTED THIS
 REVIEW, NOA 17-1102.21 IS ECO-GUARD 300 ALUMINUM FIXED
 WINDOW SMALL MISSILE IMPACT EXPIRED AS OF 1/29/2020.
  
 22) SHEET P2 THE ROOF DRAINAGE PLAN IT APPEARS THERE
 ARE 2-3-INCH ROOF DRAINS AND ASSOCIATED ROOF LEADERS.
 THE ROOF DRAINAGE PLAN DOES NOT SHOW ANY REQUIRED
 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS SEE
 2020 FBC-BUILDING CODE 1503.4.1.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER