Plan Review Notes
Plan Review Notes For Permit 21100037
Permit Number 21100037
Review Stop E
Sequence Number 1
Notes
Date Text
2022-01-31 10:47:21ELECTRICAL AUDIT OF PLANS FAILED
 1) PANEL SCHEDULES DENOTE SEVERAL CIRCUITS SUPPLYING
 SEPARATE STRUCTURE WHICH IS NOT IN COMPLIANCE WITH NEC
 225.30
 2) ELECTRICAL RISER DENOTES AN EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO MAIN DISCONNECT WHICH IS NOT IN
 COMPLIANCE WITH NEC 250.30(A)(1)
  