| Plan Review Notes For Permit 21100037 |
| Permit Number |
21100037 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-31 10:47:21 | ELECTRICAL AUDIT OF PLANS FAILED | | | 1) PANEL SCHEDULES DENOTE SEVERAL CIRCUITS SUPPLYING | | | SEPARATE STRUCTURE WHICH IS NOT IN COMPLIANCE WITH NEC | | | 225.30 | | | 2) ELECTRICAL RISER DENOTES AN EQUIPMENT GROUNDING | | | CONDUCTOR FROM METER TO MAIN DISCONNECT WHICH IS NOT IN | | | COMPLIANCE WITH NEC 250.30(A)(1) | | | | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|