2022-01-10 11:22:51ELECTRICAL AUDIT:
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
 METER HAS A #3 GROUND COMING TO MAIN NOT NEEDED ON
 SERVICE CONDUCTORS.
  
 PANELS FED FROM THE 400A DISCONNECT SHALL OVERCURRENT
 DEVICES PER 240,21(B)(1)(1)(B).
  
 240.21(A)(1) TAPS NOT OVER 3 M (10 FT) LONG. IF THE
 LENGTH OF THE TAP
 CONDUCTORS DOES NOT EXCEED 3 M (10 FT) AND THE TAP
 CONDUCTORS
 COMPLY WITH ALL OF THE FOLLOWING:
 (1) THE AMPACITY OF THE TAP CONDUCTORS IS
 A. NOT LESS THAN THE COMBINED CALCULATED LOADS ON THE
 CIRCUITS SUPPLIED BY THE TAP CONDUCTORS, AND
 B. NOT LESS THAN THE RATING OF THE EQUIPMENT CONTAINING
 AN OVERCURRENT DEVICE(S) SUPPLIED BY THE TAP CONDUCTORS
 OR NOT LESS THAN THE RATING OF THE OVERCURRENT
 PROTECTIVE DEVICE AT THE TERMINATION OF THE TAP
 CONDUCTORS.