| Notes |
| Date |
Text |
| 2022-01-10 11:22:51 | ELECTRICAL AUDIT: | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | METER HAS A #3 GROUND COMING TO MAIN NOT NEEDED ON | | | SERVICE CONDUCTORS. | | | | | | PANELS FED FROM THE 400A DISCONNECT SHALL OVERCURRENT | | | DEVICES PER 240,21(B)(1)(1)(B). | | | | | | 240.21(A)(1) TAPS NOT OVER 3 M (10 FT) LONG. IF THE | | | LENGTH OF THE TAP | | | CONDUCTORS DOES NOT EXCEED 3 M (10 FT) AND THE TAP | | | CONDUCTORS | | | COMPLY WITH ALL OF THE FOLLOWING: | | | (1) THE AMPACITY OF THE TAP CONDUCTORS IS | | | A. NOT LESS THAN THE COMBINED CALCULATED LOADS ON THE | | | CIRCUITS SUPPLIED BY THE TAP CONDUCTORS, AND | | | B. NOT LESS THAN THE RATING OF THE EQUIPMENT CONTAINING | | | AN OVERCURRENT DEVICE(S) SUPPLIED BY THE TAP CONDUCTORS | | | OR NOT LESS THAN THE RATING OF THE OVERCURRENT | | | PROTECTIVE DEVICE AT THE TERMINATION OF THE TAP | | | CONDUCTORS. |
|