| Notes |
| Date |
Text |
| 2021-10-06 15:35:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) CIRCLE OR HI-LITE THE MECHANICALLY ATTACHED BASE | | | SHEET FASTENING AND MAXIMUM DESIGN PRESSURE FROM THE | | | ONES LISTED IN SECTION 5.8.3.2 OF THE TILE UNDERLAYMENT | | | PRODUCT APPROVAL. THE REQUIRED PRESSURE IS -69.7 PSF. | | | SELECT ANY OF THE ONES THAT HAVE A MAXIMUM DESIGN | | | PRESSURE THAT IS MORE THAN THAT. FBC AMENDMENTS 107.2.1 |
|