| 2021-11-03 10:05:17 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) IT DOES NOT APPEAR THAT THE GENERATOR EXHAUST IS | | | LOCATED MORE THAN 10 FEET FROM THE BUILDING. THE | | | GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 FEET | | | FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1 PLEASE | | | SPECIFY THIS ON THE SURVEY. |
|