2022-02-15 10:27:48OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE DOOR (18078) LOCATED IN THE FIRE
 RATED WALLS TO BE FIRE RATED PER FBC 716
  
 2) DRAWING (A2-31) DETAIL H SHOWS (18") FOR THE CENTER
 OF THE TOILET PAPER HOLDER TO THE FACE OF THE TOILET -
 PLEASE CORRECT - ACCESSIBLE RESTROOMS - DRAWING A0-00D
 - PLEASE SHOW THE DIMENSION OF THE TOILET PAPER HOLDER
 FROM THE FACE OF THE TOILET TO THE CENTER OF THE TOILET
 PAPER HOLDER - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3) PLEASE USE THE WORDS "REFLECTING OR REFLECTIVE"
 SURFACE - ACCESSIBLE RESTROOM - DRAWING A0-00D - FOR
 THE MIRROR PLEASE SHOW THE DIMENSION FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACE FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) PLEASE PROVIDE THE ROOF TOP MECHANICAL SCREENING
 DETAILS FROM A DESIGN PROFESSIONAL TO MEET THE WIND
 LOADS FBC 1609
 ROOF TOP SCREENING DETAILS MAY BE DEFERRED SUBMITTALS
 BY LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.