| 2022-01-25 17:32:48 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21100004 |
| | 1/25/22 |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS. |
| | |
| | 1) FAILED. SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED |
| | SERVICE SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND |
| | SHOW THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P. |
| | LOCATIONS OF SERVICE SINKS NOT SHOWN. |
| | |
| | 7) FAILED. P-600: PROVIDE UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAILS FOR SEALING THE ANNULAR |
| | SPACES AROUND PLUMBING PIPING PENETRATING THE SLABS- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. NOT |
| | PROVIDED. |
| | |
| | 8) FAILED. A2-30 & A2-31: REFER TO SECTION 213 AND |
| | PROVIDE THE FOLLOWING FBC ACCESSIBILITY COMPLIANCE |
| | DETAILS: THE RESPONSE NARRATIVE REFERENCES SHEETS |
| | A0-00D & A5-40. SHEET A00-00D SHOWS STANDARD ADA |
| | DETAILS SOME OF WHICH ARE NOT CONSISTENT WITH THE FBC |
| | ACC WHICH IS THE GOVERNING CODE IN THE STATE OF |
| | FLORIDA. SHEET A5-40 PROVIDES ONLY KNEE AND TOE |
| | CLEARANCES FOR A RESTROOM SINK AND DOES NOT SPECIFY |
| | WHICH SINKS SHOULD BE INSTALLED ACCORDING TO THE |
| | DETAIL- SITE SPECIFIC DETAILS ARE REQUIRED. THE |
| | PROPOSED INSTALLATIONS SHALL BE IN COMPLIANCE WITH THE |
| | FOLLOWING FBC ACC CODE SECTIONS. REVISE THE PLANS |
| | ACCORDINGLY. |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. SHOW THE DIAGRAMS AT ALL |
| | SINKS SPECIFIED AS ACCESSIBLE. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. SHOW THE DIAGRAMS AT ALL |
| | WATER CLOSETS SPECIFIED AS ACCESSIBLE. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. SHOW THE |
| | DIAGRAMS IN ALL ACCESSIBLE RESTROOMS. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. SHOW THE CENTERLINES OF ALL WATER |
| | CLOSETS SPECIFIED AS ACCESSIBLE. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. SHOW THE HEIGHT MEASURMENTS AT |
| | ALL WATER CLOSETS SPECIFIED AS ACCESSIBLE. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. PROVIDE A LIST |
| | OF ACCESSIBLE LAVATORIES ON THE DETAIL. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3. NOT PROVIDED ON |
| | A0-00D. |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. THE STANDARD DETAILS ON |
| | A0-00D SHOW THE MEASUREMENTS TO THE CENTERLINES OF THE |
| | GRAB BARS. MEASUREMENTS SHALL BE TO THE TOPS OF THE |
| | GRIPPING SURFACES. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. NOT PROVIDED |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. INCORRECTLY SHOWN ON A0-00D. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. PROVIDE A LIST OF ACCESSIBLE LAVATORIES ON THE |
| | DETAIL |
| | |
| | 9) FAILED. A3-70, 71, 72, & 73- REFER TO PROVIDE THE |
| | FOLLOWING FBC ACC COMPLIANCES: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER |
| | FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES- |
| | SECTIONS 606.2 & 305. NOT PROVIDED. |
| | C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE |
| | MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308. |
| | NOT PROVIDED. |
| | D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS, |
| | MICROWAVES ETC.- SECTION 309. NOT PROVIDED. |
| | |
| | NEW COMMENTS BASED ON RESUBMITTED PLANS |
| | |
| | 1) P-400: S3 SINKS IN GN RR 18069, 18070, 18074, 18075 |
| | ARE MISLABELED AS S1 SINKS IN THE CLOUDED SANITARY |
| | RISER |
| | |
| | 2) SHEET P-600: PLEASE PROVIDE ACCESSIBILITY COMPLIANCE |
| | NOTES WHERE REQUIRED IN THE PLUMBING FIXTURE SCHEDULE- |
| | SEC. 404.1 FBC P. SEE COMMENT #8 ABOVE. THE PLANS DO |
| | NOT CLEARLY ADDRESS WHICH RESTROOMS AND FIXTURES ARE TO |
| | BE ACCESSIBLE. |
| | |
| | 3) P600 DEFFERRED SUBMITTALS: PROVIDE A LIST OF |
| | DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE |
| | LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES |
| | AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS |
| | SPECIFIED ON THE PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |