Plan Review Notes
Plan Review Notes For Permit 21100004
Permit Number 21100004
Review Stop P
Sequence Number 2
Notes
Date Text
2022-01-25 17:32:482ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21100004
 1/25/22
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS.
  
 1) FAILED. SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED
 SERVICE SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND
 SHOW THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P.
 LOCATIONS OF SERVICE SINKS NOT SHOWN.
  
 7) FAILED. P-600: PROVIDE UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAILS FOR SEALING THE ANNULAR
 SPACES AROUND PLUMBING PIPING PENETRATING THE SLABS-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. NOT
 PROVIDED.
  
 8) FAILED. A2-30 & A2-31: REFER TO SECTION 213 AND
 PROVIDE THE FOLLOWING FBC ACCESSIBILITY COMPLIANCE
 DETAILS: THE RESPONSE NARRATIVE REFERENCES SHEETS
 A0-00D & A5-40. SHEET A00-00D SHOWS STANDARD ADA
 DETAILS SOME OF WHICH ARE NOT CONSISTENT WITH THE FBC
 ACC WHICH IS THE GOVERNING CODE IN THE STATE OF
 FLORIDA. SHEET A5-40 PROVIDES ONLY KNEE AND TOE
 CLEARANCES FOR A RESTROOM SINK AND DOES NOT SPECIFY
 WHICH SINKS SHOULD BE INSTALLED ACCORDING TO THE
 DETAIL- SITE SPECIFIC DETAILS ARE REQUIRED. THE
 PROPOSED INSTALLATIONS SHALL BE IN COMPLIANCE WITH THE
 FOLLOWING FBC ACC CODE SECTIONS. REVISE THE PLANS
 ACCORDINGLY.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3. SHOW THE DIAGRAMS AT ALL
 SINKS SPECIFIED AS ACCESSIBLE.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. SHOW THE DIAGRAMS AT ALL
 WATER CLOSETS SPECIFIED AS ACCESSIBLE.
 C) TURNING SPACE DIAMETERS- SECTION 304.3. SHOW THE
 DIAGRAMS IN ALL ACCESSIBLE RESTROOMS.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2. SHOW THE CENTERLINES OF ALL WATER
 CLOSETS SPECIFIED AS ACCESSIBLE.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4. SHOW THE HEIGHT MEASURMENTS AT
 ALL WATER CLOSETS SPECIFIED AS ACCESSIBLE.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3. PROVIDE A LIST
 OF ACCESSIBLE LAVATORIES ON THE DETAIL.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3. NOT PROVIDED ON
 A0-00D.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE STANDARD DETAILS ON
 A0-00D SHOW THE MEASUREMENTS TO THE CENTERLINES OF THE
 GRAB BARS. MEASUREMENTS SHALL BE TO THE TOPS OF THE
 GRIPPING SURFACES.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6. NOT PROVIDED
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. INCORRECTLY SHOWN ON A0-00D.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2. PROVIDE A LIST OF ACCESSIBLE LAVATORIES ON THE
 DETAIL
  
 9) FAILED. A3-70, 71, 72, & 73- REFER TO PROVIDE THE
 FOLLOWING FBC ACC COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER
 FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES-
 SECTIONS 606.2 & 305. NOT PROVIDED.
 C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE
 MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308.
 NOT PROVIDED.
 D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS,
 MICROWAVES ETC.- SECTION 309. NOT PROVIDED.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS
  
 1) P-400: S3 SINKS IN GN RR 18069, 18070, 18074, 18075
 ARE MISLABELED AS S1 SINKS IN THE CLOUDED SANITARY
 RISER
  
 2) SHEET P-600: PLEASE PROVIDE ACCESSIBILITY COMPLIANCE
 NOTES WHERE REQUIRED IN THE PLUMBING FIXTURE SCHEDULE-
 SEC. 404.1 FBC P. SEE COMMENT #8 ABOVE. THE PLANS DO
 NOT CLEARLY ADDRESS WHICH RESTROOMS AND FIXTURES ARE TO
 BE ACCESSIBLE.
  
 3) P600 DEFFERRED SUBMITTALS: PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE
 LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES
 AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS
 SPECIFIED ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  