2021-11-18 08:05:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21100004
 11/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED SERVICE
 SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND SHOW
 THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P.
  
 2) A0-18: PLEASE PROVIDE THE CORRECT NUMBER OF WATER
 CLOSET AND LAVATORY FIXTURES PROVIDED BASED ON THE NEW
 BATHROOMS BEING INSTALLED ON THE FLOOR- TABLE 403.1 FBC
 P.
  
 3) P-001: PROVIDE A SANITARY DRAINAGE VENT ISOMETRIC
 DRAWING- SECTION 107.3.5.1.3 WPB.
  
 4) P-400 & P-600: PLEASE ADD W5 & W6 TO THE FIXTURE
 SCHEDULE- SECTION 107.2.1 WPB.
  
 5) P-400 & P-600: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P.
 CLARIFY THE NOTE UNDER THE WH SCHEDULE ABOUT THE HOLBY
 TEMPERING VALVES. ARE THESE VALVES TEMPERATURE LIMITING
 DEVICES THAT CONFORM TO ASSE 1070 AS REQUIRED BY
 SECTION 607.1.2 FBC P? PLEASE SHOW THEIR LOCATIONS ON
 THE RISER.
  
 6) P-600: PLEASE PROVIDE A DEVICE SCHEDULE FOR WATER
 HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS
 AND TRAP PRIMERS- SECTIONS 604.9, 807.2.1, 608.3, AND
 1002.4.1 FBC P.
  
 7) P-600: PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAILS FOR SEALING THE ANNULAR SPACES AROUND
 PLUMBING PIPING PENETRATING THE SLABS- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 8) A2-30 & A2-31: REFER TO SECTION 213 AND PROVIDE THE
 FOLLOWING FBC ACCESSIBILITY COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 9) A3-70, 71, 72, & 73- REFER TO PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER
 FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES-
 SECTIONS 606.2 & 305.
 B) KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES TO
 SINKS BASED ON COMMENT ABOVE AND SECTIONS 606.2, 305, &
 306.
 C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE
 MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308.
 D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS,
 MICROWAVES ETC.- SECTION 309.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  