| 2021-11-18 08:05:11 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21100004 |
| | 11/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED SERVICE |
| | SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND SHOW |
| | THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P. |
| | |
| | 2) A0-18: PLEASE PROVIDE THE CORRECT NUMBER OF WATER |
| | CLOSET AND LAVATORY FIXTURES PROVIDED BASED ON THE NEW |
| | BATHROOMS BEING INSTALLED ON THE FLOOR- TABLE 403.1 FBC |
| | P. |
| | |
| | 3) P-001: PROVIDE A SANITARY DRAINAGE VENT ISOMETRIC |
| | DRAWING- SECTION 107.3.5.1.3 WPB. |
| | |
| | 4) P-400 & P-600: PLEASE ADD W5 & W6 TO THE FIXTURE |
| | SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 5) P-400 & P-600: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P. |
| | CLARIFY THE NOTE UNDER THE WH SCHEDULE ABOUT THE HOLBY |
| | TEMPERING VALVES. ARE THESE VALVES TEMPERATURE LIMITING |
| | DEVICES THAT CONFORM TO ASSE 1070 AS REQUIRED BY |
| | SECTION 607.1.2 FBC P? PLEASE SHOW THEIR LOCATIONS ON |
| | THE RISER. |
| | |
| | 6) P-600: PLEASE PROVIDE A DEVICE SCHEDULE FOR WATER |
| | HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS |
| | AND TRAP PRIMERS- SECTIONS 604.9, 807.2.1, 608.3, AND |
| | 1002.4.1 FBC P. |
| | |
| | 7) P-600: PROVIDE UL TESTED AND APPROVED FIRESTOPPING |
| | ASSEMBLY DETAILS FOR SEALING THE ANNULAR SPACES AROUND |
| | PLUMBING PIPING PENETRATING THE SLABS- SECTION 315.1 |
| | FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 8) A2-30 & A2-31: REFER TO SECTION 213 AND PROVIDE THE |
| | FOLLOWING FBC ACCESSIBILITY COMPLIANCE DETAILS: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SECTION 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 9) A3-70, 71, 72, & 73- REFER TO PROVIDE THE FOLLOWING |
| | FBC ACC COMPLIANCES: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER |
| | FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES- |
| | SECTIONS 606.2 & 305. |
| | B) KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES TO |
| | SINKS BASED ON COMMENT ABOVE AND SECTIONS 606.2, 305, & |
| | 306. |
| | C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE |
| | MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308. |
| | D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS, |
| | MICROWAVES ETC.- SECTION 309. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |